Page 148 - MCCB-XT5
P. 148
ABB | SACE Tmax XT
Connections For references about the connection and terminals, please consult document 1SdM000005A1001; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication
bus.
To connect the module to Ekip Supply and Ekip Cartridge, please consult document 1SdH002009A1503.
Power supply Ekip Com Profinet is supplied directly by the Ekip Supply module to which it is connected.
NOTE: communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Interface the module has three signaling leds:
2 1
Figure 47
LEDs Description
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
Power
and communication with Trip unit present
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent.
Indicates the communication state:
Link (1) • off: incorrect connection, signal absent.
• on steady: connection correct
Indicates the communication state:
Activity (2) • off: no activity on line
• flashing: activity on line present (receiving and/or transmitting)
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
is available in the Settings menu (page 35).
The following information will be available in the About-Modules menu if Ekip Touch has detected the
module correctly:
Information Description
SN and version Identifier and SW version of the module
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
MAC address
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
146 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 External electronic accessories | 8 - Ekip Com Profinet