Page 143 - MCCB-XT5
P. 143

ABB | SACE Tmax XT

       7 - Ekip Com Modbus TCP



                                    Ekip Com Modbus TCP is a communication accessory which allows Ekip Touch to be integrated into an
                                    Ethernet network with Modbus TCP communication protocol, with remote supervision and monitoring
                                    functions.
                                    The module is configured as master and remotely, you can:
                                     •  read Ekip Touch measurements and information
                                     •  manage certain controls, including opening and closing the actuator
                                     •  access information and parameters not available on the display
                                     •  If connected to a withdrawable version of the circuit-breaker, the allows the racked-in/racked-out
                                       status to be detected
                                           NOTE: the remote open and close commands of the circuit-breaker can only be executed if
                                           Ekip Touch is in the Remote configuration
                                    The System Interface document is available for mapping the module in its communication network. All the
                                    required communication and command details are listed in the document (page 129).
                                    Accessories Ekip Cartridge and Ekip Supply are required in order to connect Ekip Com Modbus TCP  to
                                                                                                                TM
                                    Ekip Touch (page 130, 131).
                                    Depending on the parameter settings, described in the next pages, the ports used by the module are:

                                     Port         Service      Notes
                                     502/tcp      Modbus TCP   Valid for the Modbus TCP mode
                                     319/udp      IEEE 1588    Valid with IEEE 1588 protocol enabled
                                     20/udp
                                     68/udp       DHCP client  DHCP client enabled alternatively as: Static address = On




           Safety and cyber security Since the module allows the actuator connected to Ekip Touch and access to the data in the unit to be
                                    checked, it can only be connected to networks equipped with all the necessary security and prevention
                                    measures against unauthorized access (for example, the network of the control system of an installation).
                                           IMPORTANT:
                                            •  it is the customer's sole responsibility to provide and continuously ensure a secure
                                              connection between the module and customer network or any other network (as the case
                                              may be). The plant manager must establish and maintain appropriate measures (such as
                                              but not limited to the installation of firewalls, application of authentication measures,
                                              encryption of data, installation of antivirus programs, etc.) to protect the product,
                                              the network, the customer system and interface against any kind of security breaches,
                                              unauthorized access, interference, intrusion, loss and/or theft of data or information.
                                              ABB and its affiliates are not liable for damages and/or losses related to such security
                                              breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or
                                              information.
                                            •  The  module  cannot  be  connected  directly  to  the  Internet.  Only  connect  to  dedicated
                                              Ethernet networks with Modbus TCP communication protocol


                            Models Two different modules compatible with the Modbus TCP protocol are available: Ekip Com Modbus TCP
                                    and Ekip Com Modbus TCP Redundant.
                                    The modules are identical in terms of characteristics and installation methods, except for: display menus,
                                    cabling and addresses for system communication, which are specific for each module.
                                           NOTE: if different indications are not given, the information in the next chapter is valid for
                                           both models

                                    The two modules can be connected at the same time to Ekip Touch so as to expand the potential of the
                                    unit (e.g. for applications where high grid reliability is required).
                                           IMPORTANT: each Ekip Touch can be fitted with only one module per type. The configuration
                                           with two modules of the same model is not allowed (example: two Ekip Com Modbus TCP
                                           Redundant)







       141 | © 2022 ABB |  1SDH002039A1002 - ECN000212994              External electronic accessories | 7 - Ekip Com Modbus TCP
   138   139   140   141   142   143   144   145   146   147   148