Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the
module correctly:
Information Description
SN and version Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the time
of connection to the network in the case of configuration with a dynamic IP, or
IP address can be set via the menu in the event of a static IP
NOTE: without a DHCP server, the module automatically adopts a random
IP address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which the
Network Mask modules belong and enables modules to be searched for within a defined set
of recipients.
IP address of the node to which the module is connected, in the presence of
Gateway address
several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal
MAC address
to ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Enable IEEE Allows the IEEE 1588 protocol for distribution of the clock and
1558 synchronization signal to be enabled . OFF
(1)
IEEE 1558 Enables the module to be set up as a master in the the network
Master segment to which it belongs (synchronization clock). OFF
IEEE 1558 Delay Allows the data exchange mode between module and master, End-to-End
mechanism either Peer-to-Peer or End-to-End, to be selected.
Enable client Allows the SNTP protocol for distribution of the clock and OFF
SNTP synchronization signal to be enabled (1)
ANTP Server Allows the network server that supplies the SNTP to be set. 0.0.0.0
address
Time zone Defines the time zone to be used for synchronism +00:00
Daylight Saving Used to select whether daylight saving time is present (ON) or OFF
Time not (OFF) in the country to which the synchronization time refers
Parameter useful if an IEEE 1588 GrandMaster clock is not
available:
• If enabled (ON), the module is seen as an IEEE1588 master
IEEE 1588 clock by all the slaves/devices in the same local network, even OFF
Boundary clock when the source of external synchronism is different from IEEE
1588 (SNTP for example)
• If disabled (OFF) the module benefits from the synchronism of
the master in its own network
Enable Enables the Rate limiter function, which limits the number of
package packages entering the module from the network, to be activated/ Disable
Limitation deactivated
(1) Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
HW and Boot version General module information
Flash CRC status and result Information about the correctness of the SW in the module
Ekip Link status Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server Synchronization State of synchronism with SNTP server
Valid with Master IEEE 1588= ON, notifies the presence (Slave
IEEE 1558 status or PTP Master Active) or absence (PTP Master but Passive) of a
higher level master
150 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 External electronic accessories | 9 - Ekip Com EtherNet/IP TM