              Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Parameter        Description                                         Default
                                     Preferred        If several configuration files are present, allows file hierarchy   .cid
                                     configuration file  between .cid and .iid to be defined
                                                      Allows the IEEE 1588 protocol for distribution of the clock and
                                     Enable IEEE 1558                                                     OFF
                                                      synchronization signal to be enabled .
                                                                                    (1)
                                     IEEE 1558 Master  Enables the module to be set up as a master in the the network   OFF
                                                      segment to which it belongs (synchronization clock).
                                     IEEE 1558 Delay   Allows the data exchange mode between module and master,   End-to-
                                     mechanism        either Peer-to-Peer or End-to-End, to be selected.  End
                                     Time zone        Defines the time zone to be used for synchronism    +00:00
                                     Daylight Saving Time  Used to select whether daylight saving time is present (ON) or   OFF
                                                      not (OFF) in the country to which the synchronization time refers
                                                      Defines the file loading procedure:
                                                       • TFTP always On = port open, loading always possible
                                                       • TFTP enable required = port normally closed. To start loading,   TFTP
                                     TFTP Security level                                                  always
                                                      Enable TFTP must be run at the start of the procedure and
                                                      Disable TFTP must be run at the end of the procedure (disable   On
                                                      not necessary, security command).
                                                      Defines the limitations to remote opening and closing command
                                                      execution:
                                                       • Standard commands = standard commands (unrestricted)
                                     CB Open/CB Close   activated                                         Standard
                                     command           • CB operate request = standard commands not activated. Use   commands
                                                      programmable functions YC COMMAND and YO COMMAND,
                                                      and Request breaker open (28) and Request breaker close (29)
                                                      commands
                                                      Analysis of selectivity input from IEC 61850 module can be
                                     Zone Selectivity   enabled/disabled for each of protections S, S2, G, Gext, D, D(BW),   Disabled
                                     Analysis                                                             (all)
                                                      D(FW)
                                                      Parameter useful if an IEEE 1588 GrandMaster clock is not
                                                      available:
                                                       • If enabled (ON), the module is seen as an IEEE1588 master
                                     IEEE 1588 Boundary  clock by all the slaves/devices in the same local network, even   OFF
                                     clock            when the source of external synchronism is different from IEEE
                                                      1588 (SNTP for example)
                                                       • If disabled (OFF) the module benefits from the synchronism of
                                                      the master in its own network
                                                      Enables the Rate limiter function, which limits the number of
                                      Enable package   packages entering the module from the network, to be activated/ Disable
                                     Limitation
                                                      deactivated
                                    (1)  Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time


                Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Information               Description
                                     HW and Boot version       General module information
                                     Flash CRC status and result  Information about the correctness of the SW in the module
                                     Ekip Link status          Signals Ethernet cable connection errors
                                     SNTP Server Error         Error in communication with SNTP server
                                     SNTP Server Synchronization  State of synchronism with SNTP server
                                                               Valid with Master IEEE 1588= ON, notifies the presence (Slave
                                     IEEE 1558 status          or PTP Master Active) or absence (PTP Master but Passive) of a
                                                               higher level master
                                     GOOSE Missing             Signals that an expected GOOSE has not been received
                                     Configure Mismatch
                                     Decode Error              A GOOSE received does not conform to the expected structure
                                     Sequence number error
                                     Remote programmable statuses
                                     (from E to R)             Condition (true/false) of the programmable states and information on selectivity
                                                               arising from logic defined in the configuration files loaded in module IEC 61850