Page 156 - MCCB-XT5
P. 156
ABB | SACE Tmax XT
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Preferred If several configuration files are present, allows file hierarchy .cid
configuration file between .cid and .iid to be defined
Allows the IEEE 1588 protocol for distribution of the clock and
Enable IEEE 1558 OFF
synchronization signal to be enabled .
(1)
IEEE 1558 Master Enables the module to be set up as a master in the the network OFF
segment to which it belongs (synchronization clock).
IEEE 1558 Delay Allows the data exchange mode between module and master, End-to-
mechanism either Peer-to-Peer or End-to-End, to be selected. End
Time zone Defines the time zone to be used for synchronism +00:00
Daylight Saving Time Used to select whether daylight saving time is present (ON) or OFF
not (OFF) in the country to which the synchronization time refers
Defines the file loading procedure:
• TFTP always On = port open, loading always possible
• TFTP enable required = port normally closed. To start loading, TFTP
TFTP Security level always
Enable TFTP must be run at the start of the procedure and
Disable TFTP must be run at the end of the procedure (disable On
not necessary, security command).
Defines the limitations to remote opening and closing command
execution:
• Standard commands = standard commands (unrestricted)
CB Open/CB Close activated Standard
command • CB operate request = standard commands not activated. Use commands
programmable functions YC COMMAND and YO COMMAND,
and Request breaker open (28) and Request breaker close (29)
commands
Analysis of selectivity input from IEC 61850 module can be
Zone Selectivity enabled/disabled for each of protections S, S2, G, Gext, D, D(BW), Disabled
Analysis (all)
D(FW)
Parameter useful if an IEEE 1588 GrandMaster clock is not
available:
• If enabled (ON), the module is seen as an IEEE1588 master
IEEE 1588 Boundary clock by all the slaves/devices in the same local network, even OFF
clock when the source of external synchronism is different from IEEE
1588 (SNTP for example)
• If disabled (OFF) the module benefits from the synchronism of
the master in its own network
Enables the Rate limiter function, which limits the number of
Enable package packages entering the module from the network, to be activated/ Disable
Limitation
deactivated
(1) Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
HW and Boot version General module information
Flash CRC status and result Information about the correctness of the SW in the module
Ekip Link status Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server Synchronization State of synchronism with SNTP server
Valid with Master IEEE 1588= ON, notifies the presence (Slave
IEEE 1558 status or PTP Master Active) or absence (PTP Master but Passive) of a
higher level master
GOOSE Missing Signals that an expected GOOSE has not been received
Configure Mismatch
Decode Error A GOOSE received does not conform to the expected structure
Sequence number error
Remote programmable statuses
(from E to R) Condition (true/false) of the programmable states and information on selectivity
arising from logic defined in the configuration files loaded in module IEC 61850
Zone selectivity remote inputs
154 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 External electronic accessories | 10 - Ekip Com IEC 61850