       2 - Ekip Com Modbus TCP



                                    Ekip Com Modbus TCP is a communication accessory which allows Ekip Touch to be integrated into an
                                    Ethernet network with Modbus TCP communication protocol, with remote supervision and monitoring
                                    functions.
                                    The module is configured as master and remotely, you can:
                                     •  read Ekip Touch measurements and information
                                     •  provide information about the status of the circuit-breaker (open, closed, tripped)
                                     •  manage certain controls, including opening and closing the actuator (MOE-E)
                                     •  access information and parameters not available on the display
                                           NOTE: the remote open and close commands of the circuit-breaker can only be executed if
                                           Ekip Touch is in the Remote configuration

                                    The System Interface document is available for mapping the module in its communication network. All the
                                    required communication and command details are listed in the document (page 129).
                                    Depending on the parameter settings, described in the next pages, the ports used by the module are:
                                     Port         Service      Notes
                                     502/TCP      Modbus TCP   Valid for the Modbus TCP mode
                                     319/UDP      IEEE 1588    Valid with IEEE 1588 protocol enabled
                                     320/UDP
                                     68/UDP       DHCP client  DHCP client enabled alternatively as: Static address = On


                                           IMPORTANT: each circuit-breaker can house one module only; configuration with external
                                           communication modules is not allowed if an internal module is present.



           Safety and cyber security Since the module allows the actuator connected to Ekip Touch and access to the data in the unit to be
                                    checked, it can only be connected to networks equipped with all the necessary security and prevention
                                    measures against unauthorized access (for example, the network of the control system of an installation).
                                           IMPORTANT:
                                            •  it is the customer's sole responsibility to provide and continuously ensure a secure
                                              connection between the module and customer network or any other network (as the case
                                              may be). The plant manager must establish and maintain appropriate measures (such as
                                              but not limited to the installation of firewalls, application of authentication measures,
                                              encryption of data, installation of antivirus programs, etc.) to protect the product,
                                              the network, the customer system and interface against any kind of security breaches,
                                              unauthorized access, interference, intrusion, loss and/or theft of data or information.
                                              ABB and its affiliates are not liable for damages and/or losses related to such security
                                              breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or
                                              information.
                                            •  The  module  cannot  be  connected  directly  to  the  Internet.  Only  connect  to  dedicated
                                              Ethernet networks with Modbus TCP communication protocol


                       Connections To connect the module to its communication network and for references about the terminals, please
                                    consult document 1SdM000005A1001.
                                    The module is supplied with a 1-meter length cable and cabled RJ45 connector for interfacing with its
                                    network.
                                    To connect the module to Ekip Touch, please consult document 1SdH002011A1503.



















       181 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                      Internal accessories | 2 - Ekip Com Modbus TCP