Page 184 - MCCB-XT5
P. 184

ABB | SACE Tmax XT

                      Power supply Ekip Com Modbus TCP is supplied directly by the Ekip Touch module to which it is connected.
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence
                                           of auxiliary power supply


            Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
                                    is available in the Settings menu (page 129).
                                    The following communication parameters can be configured if the module has been correctly detected by
                                    Ekip Touch in the Settings-Modules menu:
                                     Parameter             Description                                  Default
                                                           Defines whether the module has the dynamic (Off) or
                                     Static IP address ON  static (On) IP address.                      Off
                                                           Se = On all the associated parameters are enabled
                                     Static address IP address  Enables the static IP to be selected    0.0.0.0
                                     Static Network Mask   Enables the subnet mask to be selected       0.0.0.0
                                                           When there are several subnets, enables the IP address
                                     Static Gateway address  of the node to which the module is connected to be   0.0.0.0
                                                           selected




                Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the
                                    module correctly:
                                     Information    Description
                                     SN and version  Identifier and SW version of the module
                                                    Address of the module, assigned to the module by a DHCP server at the time
                                                    of connection to the network in the case of configuration with a dynamic IP, or
                                     IP address     can be set via the menu in the event of a static IP
                                                        NOTE: without a DHCP server, the module automatically adopts a random
                                                        IP address within the 169.254.xxx.xxx range
                                                    Subnet mask; identifies the method for recognizing the subnet to which the
                                     Network Mask   modules belong and enables modules to be searched for within a defined set
                                                    of recipients.
                                                    IP address of the node to which the module is connected, in the presence of
                                     Gateway address
                                                    several subnets
                                                    IP addresses of the client devices connected to the module (in the Server
                                     TCP Client 1, 2, 3
                                                    mode)
                                                    Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal
                                     MAC address
                                                    to ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device


































       182 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                      Internal accessories | 2 - Ekip Com Modbus TCP