Page 185 - MCCB-XT5
P. 185
ABB | SACE Tmax XT
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Parameter for changing the configuration of the module
from Server Only to Client and Server and for integrating it
into an interactive data exchange network (see Ekip Com
Client/Server Server only
Hub on page 159)
IMPORTANT: if Client/Server, the module allows
data exchange like a normal Server function
Allows the IEEE 1588 protocol for distribution of the clock
IEEE 1588 enable OFF
and synchronization signal to be enabled .
(1)
Enables the module to be set up as a master in the the
Master IEEE 1588 network segment to which it belongs (synchronization OFF
clock).
IEEE 1588 delay Allows the data exchange mode between module and
mechanism master, either Peer-to-Peer or End-to-End, to be selected. End-to-End
Allows the SNTP protocol for distribution of the clock and
SNTP Client enable OFF
synchronization signal to be enabled (1)
Force Static IP Allows the network server that supplies the SNTP to be 0.0.0.0
Address set.
Time zone Defines the time zone to be used for synchronism +00:00
Used to select whether daylight saving time is
Daylight Saving
Time present (ON) or not (OFF) in the country to which the OFF
synchronization time refers
Permits (Enabled ARP) the periodic generation of a
Disabilita Gratuitous ARP message, used by Ekip Connect to rapidly ARP Enabled
Gratuitous ARP find the modules via Ethernet scan without knowing the IP
address beforehand
Access protected Enables the writing operations performed via the network
by password to be protected by a password (Request password) Standard mode
Parameter useful if an IEEE 1588 GrandMaster clock is not
available:
• If enabled (ON), the module is seen as an IEEE1588
IEEE 1588 master clock by all the slaves/devices in the same local OFF
Boundary clock network, even when the source of external synchronism is
different from IEEE 1588 (SNTP for example)
• If disabled (OFF) the module benefits from the
synchronism of the master in its own network)
Enables the Rate limiter function, which limits the number
Enable package of packages entering the module from the network, to be Disable
Limitation
activated/deactivated
(1) Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(2) the parameter can only be changed via system bus in the remote configuration
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
Boot and HW version General module information
Flash CRC status e result Information about the correctness of the SW in the module
Stato Ekip Link Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server State of synchronism with SNTP server
Synchronisation
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
IEEE 1588 status Master Active) or absence (PTP Master but Passive) of the higher level
master
183 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 Internal accessories | 2 - Ekip Com Modbus TCP