Page 187 - MCCB-XT5
P. 187

ABB | SACE Tmax XT

                      Power supply Ekip Com Profinet is supplied directly by the Ekip Touch module to which it is connected.
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence
                                           of auxiliary power supply


            Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
                                    is available in the Settings menu (page 35).
                                    The following information will be available in the About-Modules menu if Ekip Touch has detected the
                                    module correctly:
                                     Information        Description
                                     SN and version     Identifier and SW version of the module
                                                        Address assigned by ABB, with OUI (Organizationally Unique Identifier)
                                     MAC address        equal to ac:d3:64, which uniquely identifies the manufacturer of an
                                                        Ethernet device




              Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Parameter    Description                                         Default
                                                  Defines Dataset (acyclic data) access mode
                                                   • each individual acyclic register can be accessed in the Legacy
                                                  mode using the Slot, Subslot and Index fields (with Slot fixed at
                                     Data access   3)                                                 Legacy
                                     mode
                                                   • only complete blocks can be accessed in the Dataset mode; Slot
                                                  is fixed at 0, Subslot at 1 and Index defines the block reference
                                                  See System Interface for details.
                                     Cyclic data   Establishes whether the register of the cyclic data item is   Little endian
                                     endianess    configured in Big endian or Little endian.
                                     Acyclic data   Establishes whether the register of the acyclic data item is   Big endian
                                     endianess    configured in Big endian or Little endian.




                Remote information Certain integrative information concerning the version and state of the module is available via service
                                    connector (via Ekip Connect) or through communication via system bus, i.e.,HW and Boot version, CRC
                                    state (correctness of SW in module), DCP Name, network settings (IP address, Network Mask, Gateway
                                    address)






































       185 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                          Internal accessories | 3 - Ekip Com Profinet
   182   183   184   185   186   187   188   189   190   191   192