Page 197 - MCCB-XT5
P. 197

ABB | SACE Tmax XT

         Remote Link configurations Regarding the Link functions, the following further parameters are available:
                                     Information        Description                                      Default
                                     Link Actor (1÷15)  IP address of each actor (from 1 to 15)          0.0.0.0
                                                        Configuration parameters of the configurable states:
                                                         • selection of actor (actor from 1 to 15) which activates the
                                     Remote Programmable   programmable status                           Actor 1
                                     Status (A÷D)                                                        Nobody
                                                         • event of the actor that determines change of
                                                        programmable status
                                                        Configuration parameters of the words:
                                     Remote Status word    • selection of actor (actor from 1 to 15) from which the word  None 1
                                     (A÷D)              status is taken                                  global
                                                         • selection of the taken word
                                                        Active (Passive diagnosis) or deactivated (No diagnosis)   No
                                     Diagnostic
                                                        cabled selectivity diagnosis                     Diagnostic
                                     Diagnostic check   30 s, 1 min, 10 min, 60 min diagnosis frequency intervals   30 seconds
                                     timeout            available, if activated
                                                        Configuration of hardware selectivity (Only HW) or hardware
                                     Zone Selectivity Type                                               HW only
                                                        and logic (Mixed)
                                     Repeat Configuration   Interactive mask for selecting selectivity to be sent also to   0x0000
                                     mask               the upper levels, even if not active in the programmed device



                Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Information               Description
                                     HW and Boot version       general module information
                                     Flash CRC status and result  Information about the correctness of the SW in the module
                                     Ekip Link status          Signals Ethernet cable connection errors
                                     SNTP Server Error         Error in communication with SNTP server
                                     SNTP Server Synchronization  State of synchronism with SNTP server
                                                               Valid with Master IEEE 1588= ON, notifies the presence (Slave or
                                     IEEE 1558 status          PTP Master Active) or absence (PTP Master but Passive) of the
                                                               higher level master




            Remote Link information Regarding the Link functions, the following further parameters are available:
                                     Information               Description
                                                               Information about the state and inconsistency of HW and logic
                                     Line Congruency detection
                                                               selectivity (state and type of selectivity inconsistent)
                                     Remote Programmable Status  state (true/false) of remote programmable states A, B, C and D
                                     Remote Status Word        value of remote programmable Words A, B, C, D
                                     Logic Zone Selectivity    Logic selectivity states (inputs and outputs)



























       195 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                                 Internal accessories | 6 - Ekip Link
   192   193   194   195   196   197   198   199   200   201   202