Page 192 - MCCB-XT5
P. 192
ABB | SACE Tmax XT
Connections To connect the module to its communication network and for references about the terminals, please
consult circuit diagrams 1SdM000005A1001.
The module is supplied with a 1-meter length cable and cabled RJ45 connector for interfacing with its
network.
To connect the module to Ekip Touch and to actuator MOE-E if present, please consult document
1SdH002011A1503.
Power supply Ekip Com IEC 61850 is supplied directly by the Ekip Touch to which it is connected.
NOTE: communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
is available in the Settings menu (page 35).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter Description Default
Defines whether the module has the dynamic (Off) or static
Static IP address ON (On) IP address. Off
Se = On all the associated parameters are enabled
Static address IP Enables the static IP to be selected 0.0.0.0
address
Static Network Mask Enables the subnet mask to be selected 0.0.0.0
When there are several subnets, enables the IP address of the
Static Gateway address 0.0.0.0
node to which the module is connected to be selected
Allows the SNTP protocol for distribution of the clock and
Enable SNTP client Off
synchronization signal to be enabled.
SNTP Server Addr. Allows the network server that supplies the SNTP to be set. 0.0.0.0
Defines the write mode of the configuration file in the
module via the TFTP port; two options are available:
• Always ON: the TFTP port is always open and write is
Configuration Session always enabled Always ON
• Activation requested: the TFTP is opened by a specific
command, which enables write for a limited time (or for a
finite number of data packages)
Write enable command on TFTP port in Activation mode
Start Configuration ---
requested
Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the
module correctly:
Information Description
SN and version Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the
time of connection to the network in the case of configuration with a
IP address dynamic IP, or can be set via the menu in the event of a static IP
NOTE: without a DHCP server, the module automatically adopts a
random IP address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which
Network Mask the modules belong and enables modules to be searched for within a
defined set of recipients.
IP address of the node to which the module is connected, in the presence
Gateway address
of several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier)
MAC address equal to ac:d3:64, which uniquely identifies the manufacturer of an
Ethernet device
Cfg file Name of the configuration file uploaded to the modules
Cfg file error Code of the error concerning the configuration file (0 = no error)
190 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 Internal accessories | 5 - Ekip Com IEC 61850