Power supply Ekip Com Hub is supplied directly by the Ekip Touch to which it is connected.
NOTE: communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
is available in the Settings menu (page 35).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter Description Default
Enable Switches communication between module and server on/off. Off
Defines whether the module has the dynamic (Off) or static (On)
Static IP IP address. Off
address ON
If = On all the associated parameters are enabled
Static address
IP address Enables the static IP to be selected 0.0.0.0
Static Network
Mask Enables the subnet mask to be selected 0.0.0.0
Static Gateway When there are several subnets, enables the IP address of the 0.0.0.0
address node to which the module is connected to be selected
Enable SNTP Allows the SNTP protocol for distribution of the clock and Off
client synchronization signal to be enabled.
SNTP Server Allows the network server that supplies the SNTP to be set. 0.0.0.0
Addr.
Password code required to register module on Cloud ---
The Remote FW update submenu enables the Firmware update function of the module to be managed;
the following parameters are available:
Parameter Description Default
Enables firmware update function of module to be remotely
Enable OFF
activated/deactivated
The parameter is available when Enable = On and allows the
automatic update mode to be activated (On): in the presence
of new Firmware, this latter is updated automatically. If the
Automatic parameter is Off, updating must be performed in the Manual OFF (manual)
mode: in the presence of new Firmware, the message Ekip
Com Hub FW Update appears in the status bar and updating is
performed via the Manual command
This parameter is available when Enable= On, with Automatic=
Start FW Off configuration and when new Firmware is present (see Little endian
update description above); allows the Firmware update of the module to
run
197 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 Internal accessories | 7 - Ekip Com Hub