P. 202

ABB | SACE Tmax XT

       8 - Ekip Signalling 1K



                                    Ekip Signalling 1K is a signaling accessory allowing programmable inputs/outputs to be managed.
                                    The module can be configured in the CB with the IEC standard.
                                           IMPORTANT: each circuit-breaker can house one module only; configuration with external
                                           modules is not allowed if an internal module is present






                       Connections The circuit diagrams and references concerning the terminals are available in document 1SdM000005A1001.
                                    To connect the module to Ekip Touch and to actuator MOE-E if present, please consult document
                                    1SdH002011A1507.



                      Power supply Ekip Signalling 1K is supplied directly by the Ekip Touch to which it is connected.
                                           WARNING! communication between Ekip Touch and the module is interrupted in the
                                           absence of auxiliary power supply



                              Input The input can be configured so that its status corresponds to actions or signals, with different
                                    programming options (see Menu).
                                    The module permits two logic statuses, interpreted differently by the Trip unit on the basis of the selected
                                    configuration:
                                                                                             Status detected by Trip
                                     State      Electrical condition  Contact configuration
                                                                                             unit
                                                                      Active open           ON
                                     Open       Circuit open  (1)
                                                                      Active closed         OFF
                                                                      Active open           OFF
                                     Close      Short-circuit  (2)
                                                                      Active closed         ON

                                    (1)  R > 100 kΩ
                                    (2)  R (wiring + short circuit contact) <25 Ω


                            Output The output has three contacts: normally open (NO), normally closed (NC) and common.
                                    The output can be configured so that the contacts change status when one or more events occur, with
                                    different programming options (see Menu).
                                    Compared to the common contact, the NO and NC contacts have the following electrical characteristics:
                                     Characteristics                        Maximum limit  (1)
                                     Maximum switchable voltage             150 VDC / 250 VAC.
                                                                            2 A @ 30 VDC, 0,8 A @ 50 VDC, 0,2 A @ 150 VDC,
                                     Breaking capacity
                                                                            4 A @ 250 VAC
                                     Dielectric strength between contact and internal   1000 V AC (1 minute @ 50 Hz).
                                     coil

                                    (1)  data relating to a resistive load



















       200 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                          Internal accessories | 8 - Ekip Signalling 1K