Page 24 - MCCB-XT5
P. 24

Continued from the previous page                               ABB | SACE Tmax XT
                                     Fault                     Possible causes           Suggestions
                                                               The PIN has been disabled or   Operating condition correct;
                                     The PIN is not required   has already been entered in the  consult chapter relating to the
                                                               same programming session  PIN
                                                                                         Contact ABB or consult
                                     PIN error                 PIN wrong or lost
                                                                                         document 1SDH001501R0001
                                                               Trip coil is not connected   Check Trip coil connection and
                                                               properly                  messages on display
                                     It is not possible to perform the  CB trip signal has not been   Press the reset pushbutton
                                     trip test                 reset
                                                               The busbar current is greater   Correct operating condition.
                                                               than zero
                                                                                         1. If closed, open CB in the
                                                                                         manual mode and check
                                                                                         changed status.
                                                                                         2. Press iTest, check that the
                                                                                         signal has disappeared from
                                                               One or more of the following   the display and the general
                                                               conditions:
                                     TRIP fail signaling: Trip Fail    • Trip coil not working  status of the alarms.
                                     command (BF)                                        3. Check the conditions of the
                                                                • status contacts not working  wiring and internal contacts
                                                                • faulty internal wiring
                                                                                         4. Working in safety conditions,
                                                                                         close the CB and perform a trip
                                                                                         test via the trip unit

                                                                                         Contact ABB if problems persist
                                     The expected trip does not   Trip excluded          Operating condition correct;
                                     occur                                               enable trip if necessary
                                                               Wrong threshold/time/curve   Correct parameters
                                                               selected
                                     Trip times different than   Thermal memory enabled  Disable it if it is not necessary
                                     expected
                                                               Zone selectivity enabled  Disable it if it is not necessary
                                                               Incorrect neutral selection  Modify the neutral selection
                                                                                         Correct operating condition
                                     Rapid trip with I3=Off    linst trip                with short circuit at high
                                                                                         current
                                                               Incorrect selection of the   Set internal or external sensor
                                                               sensor
                                     High ground-fault current, but
                                     no trip occurs            Function G inhibited owing to   Operating condition correct
                                                                                         (see protection description
                                                               high current
                                                                                         chapter)
                                                               No auxiliary power supply and/
                                     Opening data not displayed                          Correct operating condition.
                                                               or battery low