                  Check accessories The inspections to perform on the external and internal accessories, if present, before putting into service
                                    are indicated below:
                                     Accessories  Checks
                                                  1. If Ekip Cartridge is present: check the connections of all modules to Ekip Supply
                                                  and the connection between Ekip Cartridge and the lateral terminal box of the CB
                                                  For Ekip Signalling 10K and Ekip Multimeter, in the absence of Ekip Cartridge:
                                                  check the connection of the bus of the module (W3-W4) to the lateral terminal box
                                                  of the CB
                                     External     2. Power up Ekip Touch (and the external modules if there is a separate supply)
                                     modules      and make sure they are on
                                                  3. Check that the Local bus is enabled (Settings-Modules-Local Bus)
                                                  4. Check that the Power Led of each module is on like the Power Led of Ekip Touch
                                                  (steady or synchronous flash)
                                                  5. Check in the About-Modules menu to make sure that all installed modules are
                                                  present and that there are no alarms
                                                  1. make sure that module is connected to the internal terminal box
                                                  2. Make sure that the auxiliary supply is connected to the internal terminal box
                                     Internal
                                     modules      3. Power up the Trip unit and make sure it is on
                                                  4. Check in the About-Modules menu to make sure that all installed modules are
                                                  present and that there are no alarms
                                                  1. Check that the sensor is connected to the lateral terminal box of the CB in the
                                                  proper way and that the terminals are in the right direction  (1)
                                     External     2. Power up the Trip unit and make sure it is on
                                     neutral      3. Check in the Settings-Circuit-breaker menu that Configuration= 3P + N;
                                                  otherwise change the parameter
                                                  4. Make sure there are no alarms
                                                  1. Check selectivity connections (between Ekip Touch and the other units) as
                                                  shown in circuit diagrams 1SDM000002A1001
                                                  2. Provide Ekip Touch with auxiliary power and make sure that CB status is: Open
                                                  3. Check that the protection of the selectivity concerned has been enabled
                                                  (example: S protection)
                                                  4. Select the Zone Selectivity menu and the submenu of the protection concerned;
                                                  follow the instructions in points 5, 6, 7 and 8 for each protection activated
                                                      NOTE: for selectivity D, consider submenu S for the Forward connections and
                                                     G for the Backward connections
                                     Zone selectivity  Check Output:
                                                  5. Select the Force Output command and check, on the Trip unit connected to the
                                                  Ekip Touch output, that the status of its Input = ON
                                                  6. Select the Release Output command and check, on the Trip unit connected to
                                                  the Ekip Touch output, that the status of its Input = OFF
                                                  Check Input:
                                                  7. Select the Force Output command on the Trip unit connected to the Ekip Touch
                                                  input and check on Ekip Touch that the status of its Input = ON
                                                  8. Select the Release Output command on the Trip unit connected to the Ekip
                                                  Touch input and check on Ekip Touch that the status of its Input = OFF
                                                  1. Make sure that the MOE-E stored energy operating mechanism is correctly
                                                  cabled as shown in circuit diagrams 1SDM000002A1001
                                                  2. Set the circuit-breaker to the closed position
                                     MOE-E        3. Provide Ekip Touch with auxiliary power and supply the MOE-E device with rated
                                     stored energy   voltage
                                     operating
                                     mechanism    4. Perform an opening test from the Test-Test CB menu with the Open CB)
                                                  command and check that the CB has opened
                                                  5. Repeat the test from the Test-Test CB menu with the Close CB) command and
                                                  check that the CB has closed
                                     AUP circuit   1. Check that Trip unit reads status of withdrawable circuit breaker properly by
                                     breaker status  means of About-Circuit breaker-CB Status
                                     inputs, if CB is
                                     withdrawable   2. Switch status of AUP device and make sure that Trip unit reads the status
                                     version      change properly by means of About-Circuit breaker-CB status menu

                                    (1)  for details consult document 1SdH001000r0506




       18 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                      Management operations | 1 - Putting into service