Continued from the previous page                               ABB | SACE Tmax XT
                                    Parameters
                                     Parameter  Description                                             Default
                                                Activates/deactivates the protection and its availability in the
                                     Enable                                                             OFF
                                                parameters menu
                                                Activates/deactivates transmission of the open command: if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   OFF
                                                information
                                                Defines the gradient of the line relating to threshold Q24.
                                     Threshold Kq The value is given as absolute value (slope of the line) and can be set   -2
                                                within the range: -2 to 2 in 0.01 steps
                                                This is the reactive power required to define the trip line and relative
                                                TRIP area.
                                     Threshold   The value is given as both absolute value (kVAR) and relative value (Sn)
                                     -Q24       and can be set within the range: 0.1 Sn to 1 Sn in 0.001 Sn steps  0,1 Sn
                                                     NOTE: the threshold expressed in Sn is not preceded by the “-”
                                                    sign, but should still be understood as inverse reactive power
                                                Defines the gradient of the line relating to threshold Q25.
                                     Threshold
                                     Kq2        The value is given as absolute value (slope of the line) and can be set   2
                                                within the range: -2 to 2 in 0.01 steps
                                                Defines the reactive power value at which the protection trips and is
                                                required for the purpose of defining the relative TRIP area
                                     Threshold   The value is given as both absolute value (kVAR) and relative value (Sn)
                                     -Q25       and can be set within the range: 0.1 Sn to 1 Sn in 0.001 Sn steps  0,11 Sn
                                                     NOTE: the threshold expressed in Sn is not preceded by the “-”
                                                    sign, but should still be understood as inverse reactive power
                                                This is the trip time of the protection; the value is given in seconds
                                     Time t24                                                           100 s
                                                and can be set within a range: 0.5 s to 100 s, in 0.1 s steps
                                                It is the minimum voltage for activation of the protection. If a there is
                                                at least one line-to-line voltage present below the Vmin threshold, the
                                     Threshold
                                     Vmin       protection is not active.                               0.5 Un
                                                The value is given as both absolute value (V) and relative value (Un)
                                                and can be set within the range: 0.5 Un to 1.2 Un in 0.01 Un steps

                                    Limitations and additional functions
                                     •  Ekip Touch accepts parameters in accordance with the following limitations: Q24 < Q25 and Kq < Kq2
                                     •  the block functions can also be accessed by means of the service connector (via Ekip Connect) or
                                       by connection to the system bus (page 76).


                   Cos φ Protection The protection activates an alarm when the total Cos φ value drops below the set threshold.
                                    Total cos φ is calculated as ratio between total active power and total apparent power.
                                    Parameters
                                    The parameters are available in the Advanced - Signaling menu (page 33)
                                     Parameter  Description                                             Default
                                                Activates/deactivates the protection and availability of the threshold
                                     Enable                                                             OFF
                                                in the menu
                                                Defines the value that activates the protection; can be set within the
                                     Threshold                                                          0,95
                                                range: 0.5 to 0.95 in 0.01 steps