       7 - ROCOF protections
                                    The ROCOF Protection package is available by default for Ekip G Hi-Touch and configurable in the
                                    remaining models as additional SW package
                                    The protection is described below:


                  ROCOF Protection Function
                                    ROCOF protection protects against rapid frequency variations: the protection sends a TRIP command if
                  t                 the frequency changes faster than control variation f28 set in the unit for longer than t28.
                       f28    ROCOF

                                            f(Hz)                              Frequency variation
                            t28
                                                                               after failure (1)

                               Hz/s                  Frequency fluctuation
                                                     (after a failure)
                                                                                              f28

                                              f mis







                                                                                    t28          t(s)
                                    Figure 30

                                    (1)  example with positive linear variation of the higher frequency of the set f28 value; the protection
                                    also manages negative variations

                                    The protection excludes itself if the maximum value of the line-to-line voltage is less than 30 V.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 83)
                                     •  the graph with trip curve (page 98)
                                    Parameters
                                     Parameter  Description                                             Default
                                                Activates/deactivates the protection and its availability in the
                                     Enable                                                             OFF
                                                parameters menu
                                                Activates/deactivates transmission of the open command: if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   OFF
                                                information
                                                establishes the maximum admissible frequency variation rate over
                                     Threshold   time; the protection trips if this rate is exceeded.   0,6 Hz/s
                                     f28        The value is given as absolute value (Hz/s) Fn) and can be set within
                                                the range: 0.4 Hz/s to 10 Hz/s in 0.2 Hz/s steps
                                     Trip       Establishes whether the protection monitors an increase (Up), a   Up or Down
                                     Direction  decrease (Down) or both variations (Up and Down)
                                                This is the trip time of the protection; the value is given in seconds
                                     Time f28                                                           0,5 s
                                                and can be set within a range: 0.06 s to 300 s, in 0.01 s steps
                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 76).














       67 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                                Protections | 7 - ROCOF protections