                 Startup Protection The function, which can be activated for protections S, I, G, S2, D and UP (if available and enabled), allow
                                    the protection threshold (StartUp threshold) to be changed for a period that can be set by the user
                                    (Startup time).
                                           NOTE: for UP protection, startup means the time for which the protection is disabled
                                    The period begins after a threshold has been exceeded (activation threshold), user-programmable via
                                    Ekip Connect or system bus, valid and verified for all phase currents.
                                    The Startup condition elapses after Startup time and re-activates the next time the activation threshold
                                    is exceeded
                                           NOTE: startup does not occur again until at least one current remains above activation
                                           threshold level

                                    A graphic representation with S protection follows:






















                                    Figure 32




                    Block functions Six blocks can be configured for certain protections by means of the service connector (via Ekip Connect)
                                    or communication via system bus. These blocks are useful for deactivating the protections relating to
                                    programmable events:
                                     Block name            Description
                                     BlockOnProgStatusA    Block active if programmable status A is true
                                     BlockOnProgStatusB    Block active if programmable status B is true
                                     BlockOnProgStatusC    Block active if programmable status C is true
                                     BlockOnProgStatusD    Block active if programmable status D is true
                                                           Block active during StartUp time (if StartUp for the specific protection
                                     BlockOnStartUp
                                                           is available and activated)
                                     BlockOnOutOfFrequency  Block active if frequency measured is not within 30 Hz to 80 Hz range

                                    Each block is independent and has its own activation command (Block On); however, each protection can
                                    be configured with several block conditions (operation in OR logic condition).
                                    The protections which have blocks are: S, I, G, MCR, S2, D, S(V), S2(V), UV, OV, VU, UV2, OV2, UP, OP, RP, RQ,
                                    OQ, RV, UF, OF, UF2, OF2, ROCOF, UC, U, R Jam, R Stall.
                                           IMPORTANT: the blocks can cause:

                                            •  increase of protection trip times (max: + 30 ms), owing to verification of the event itself
                                              (example: (frequency check)
                                            •  undesired deactivation of the protection, if the block is associated with statuses or
                                              signals to modules via local bus and auxiliary power supply is absent. In this case, it may
                                              be useful to also consider the status of the auxiliary power supply (Supply from Vaux)
                                              when programming the event
                                            •  undesired deactivation of the protection, if the block is associated with frequency
                                              measurements and the voltage is less than the minimum calculation threshold
                                           IMPORTANT: if the function is activated, the blocks are deactivated during startup (except
                                           for BlockOnStartup, which functions during this period)




       76 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                  Protections | 10 - Additional protections and functions