Page 196 - dehn-catalogue-lightning-protection_3
P. 196

HVI Conductor

                          10  Sealing End Range, Connection to "Capping of Roof Parapet"
                         If several installation parts require protection, it is advisable not to route the HVI Conductor of each air-termination system individually to the
                         earth-termination system. The HVI Conductors from the air-termination system can be connected to the capping of the roof parapet which
                         serves as a ring conductor. From the capping of the roof parapet several down conductors can then be routed to the earth-termination system.









                                                                                                  l = sair x 2
                                                                                                 35 - max. 150 cm

                                                                                                            4


    HVI   Conductor                                                                       sair


                                                                                          l ≥ sair        3
                                                                                                    1, 2






                         Accessories for the Sealing End Range, Connection to "Capping of Roof Parapet"

         1
                         Spacer with EB element for HVI Conductor (length of variable sealing end 350-900 mm)
                         Spacer for establishing the variable sealing end of the HVI Conductor.
                         With MV clamp for connection to the equipotential bonding (Rd 16 mm / Rd 8-10 mm).
                         Concrete base (Part No. 102 010, weight 17 kg) and base plate (Part No. 102 050) must be ordered separately.
         Eurocode
                          Part No.                    105 461
                          PU                          1 pc(s)


                         Variable tripod with EB element for HVI Conductor (length of variable sealing end 900-1500 mm)
         2               Tripod (hinged) with variable spacer for establishing the sealing end of the HVI Conductor.
                         With UNI earthing clamp for connecting 1x Rd 8-10 mm and 1x conductor 4-50 mm²
                         Adjustable to the roof inclination of max. 10°.
                         The three concrete bases (Part No. 102 075, weight 8.5 kg) and the base plate (Part No. 102 060) must be ordered separately.
         Eurocode
                          Part No.                    105 469
                          PU                          1 pc(s)




         3               Spacer for HVI Conductor
                         Spacer for additional mechanical fixing in the variable sealing end range.
                         The spacer is erected with two concrete bases (Part No. 102 010, weight 17 kg). The concrete bases and the base plate (Part No. 102 050)
                         must be ordered separately.
                          Part No.                    106 815
                          PU                          1 pc(s)



         4               KS connector
                         With M10 screw and nut.
                         Lightning current carrying capabillity 200 kA (10/350 μs).
                          Part No.                    301 209
                          PU                          1 pc(s)