Page 197 - dehn-catalogue-lightning-protection_3
P. 197
HVI Conductor
10 Sealing End Range on a Building Structure
If the HVI Conductor is installed on a building structure, the calculated separation distance "s" in the sealing end range from the metal parts
in the building structure must be maintained. The sealing end range reaches from the EB connection element to the earth connection element.
If the HVI Conductor is directly connected with an earth entry rod / earth-termination system, an EB element is not necessary. The sealing
end range thus also remains unconsidered.
Air solid
material
r ≥ sair r ≥ sair x 2
1, 2
sealing end range 1500 mm r ≥ sair HVI Conductor
3
Accessories for the Sealing End Range on a Building Structure
EB connection element for HVI long Conductor
For discharging the electric field of the HVI long Conductor in the sealing end range.
Special slotted design to electrically contact the semi-conductive sheath.
Part No. 410 229
PU 1 pc(s) 1
KS connector
With screw and nut M10.
Part No. 301 019
PU 100 pc(s) 2
Disconnecting clamp
Disconnecting clamp with spring washer for connecting the HVI power Conductor with the earth entry rod.
Lightning current carrying capability 200 kA (10/350 µs).
Part No. 459 200 3
PU 1 pc(s)
Valid as of March 1, 2020 Detailed product information can be found on our website 193