HVI power Conductor
HVI power Conductor
The HVI power Conductor is the most powerful variant of the high-volt-
age-resistant, insulated down conductors (HVI Conductors). Unlike the s s
standard HVI Conductor, it allows one to maintain an equivalent separa-
tion distance of 0.9 m in air and 1.8 m in solid material. It is particularly ≤ 90 cm
important to point out that the HVI power Conductor and the correspond- < 75 cm
ing components are tested for a lightning current carrying capability of
up to 200 kA (10/350 µs) based on EN 62561-1. Therefore, this type of
conductor may be used for all classes of LPS (I-V).
This conductor is installed, above all, on buildings such as hospitals,
computing centres or silos where large separation distances need to be
maintained due to the building dimensions (height). Moreover, the con-
ductor routing to the earth-termination system can be longer.
The conductor can be installed inside a stainless steel or aluminium
supporting tube. The internal sealing end spring element automatically
contacts the semi-conductive sheath and thus provides the sealing end.
HVI power Conductor The functional equipotential bonding is directly connected to the metal
supporting tube and the structure. When using GRP/Al supporting tubes,
another HVI power Conductor can be installed outside using a connection
kit.
HVI power Conductor (pre-assembled)
In case of the pre-assembled HVI power Conductors, inside as well as
outside installation, the head piece is already assembled and shrink
wrapped. The other conductor end can be exactly positioned to suit
the structure of system using the loosely delivered connection element.
Minimum order length is 6 m, additional conductor lengths in steps of
0.5 m (max. 35 m). Conductor length to be indicated when ordering.
HVI power long Conductor (on plywood reel / cut to length)
The HVI power long Conductor for on-site assembly is available in a
length of 100 m on a disposable plywood reel (diameter approx. 900 mm,
width approx. 485 mm) or cut to length (6-35 m or 36-80 m). The installer
determines the required lengths, cuts to length and assembles the sealing
ends on site.
Technical data HVI power Conductor HVI power long Conductor HVI power long Conductor
(pre-assembled) (on plywood reel) (cut to length)
Structure stranded stranded stranded
Cross-section of inner conductor (Cu) 25 mm 2 25 mm 2 25 mm 2
Colour black black black
Outer diameter 27 mm 27 mm 27 mm
Equivalent separation distance (air) ≤ 90 cm ≤ 90 cm ≤ 90 cm
Equivalent separation distance (solid material) ≤ 180 cm ≤ 180 cm ≤ 180 cm
Minimum bending radius (OD = outer diameter) 10 x OD, 270 mm black 10 x OD, 270 mm black 10 x OD, 270 mm black
Operating temperature -50 °C ... +70 °C -50 °C ... +70 °C -50 °C ... +70 °C
Temperature for installation -5 °C ... +40 °C -5 °C ... +40 °C -5 °C ... +40 °C
Tensile strength 1200 N 1200 N 1200 N
UV stability / weather resistance yes yes yes
Tested with limp (10/350 µs) based on EN 62561-1 200 kA 200 kA 200 kA
For use in class of LPS in case of a single down conductor I, II, III, IV I, II, III, IV I, II, III, IV
without current distribution (kc = 1)
Installation in Ex zone 1 and 21 allowed allowed allowed
Minimum order quantity ≥ 6 m 100 m ≥ 6 / ≥ 36 m
Max. order length 35 m — 35 / 80 m
Cable weight / 100 m — ~ 73 kg —