Page 217 - dehn-catalogue-lightning-protection_3
P. 217
HVI power Conductor
5 Sealing End Range, Connection to "Isolated Ring Condcutor"
If several installation parts require protection, it is advisable not to route the HVI power Conductor of each air-termination system indivi-
dually to the earth-termination system. The HVI power Conductors from the air-termination system can be connected to an "isolated ring
conductor". From this "isolated ring conductor" several down conductors can then be led to the earth-termination system. The "isolated ring
conductor" must be installed, e.g. on the roof, on spacers and concrete bases, taking the calculated separation distance "s" into account.
l = sair x 2
35 - max. 180 cm
4 5
sair
l ≥ sair 1, 2 3
HVI power Conductor
Accessories for the Sealing End Range, Connection to "Isolated Ring Condcutor"
Spacer with EB element for HVI power Conductor (length of variable sealing end 350-900 mm)
Spacer for establishing the variable sealing end of the HVI power Conductor. 1
With MV clamp for connection to the equipotential bonding (Rd 16 mm / Rd 8-10 mm). Eurocode
Concrete base (Part No. 102 010, weight 17 kg) and base plate (Part No. 102 050) must be ordered separately.
Part No. 105 462
PU 1 pc(s)
Variable tripod with EB element for HVI power Conductor (length of variable sealing end 900-1800 mm)
Tripod (hinged) with variable spacer (small) for establishing the variable sealing end of the HVI power Conductor. For a variable sealing end Eurocode 2
length of 900-1500 mm (Part No. 105 468) and 1500-1800 mm (Part No. 105 467).
With UNI earthing clamp for connecting 1x Rd 8-10 mm and 1x conductor 4-50 mm². Adjustable to the roof inclination up to max. 10°. The
three concrete bases (Part No. 102 075, weight 8.5 kg) and base plates (Part No. 102 060) must be ordered separately.
Part No. 105 468 105 467
PU 1 pc(s) 1 pc(s)
Spacer for HVI power Conductor
Spacer for additional mechanical fixing in the variable sealing end range. The spacer is erected with two concrete bases (Part No. 102 010,
weight 17 kg). The concrete bases and base plate (Part No.Nr. 102 050) must be ordered separately. 3
Part No. 106 814
PU 1 pc(s)
DEHNiso spacer 4
For, e.g. air-termination tip (Part No. 101 001), air-termination tip with MV clamp (Part No. 105 071) (for crossover points) or MV clamp for
spanning cables (Part No. 105 079).
Part No. 106 217 106 220
PU 10 pc(s) 10 pc(s)
MV clamp
With hexagon screw, spring washer and thread in the base part. 5
Lightning current carrying capability 200 kA (10/350 μs).
Part No. 390 209
PU 1 pc(s)
Valid as of March 1, 2020 Detailed product information can be found on our website 213