HVI power Conductor

                          5  Sealing End Range, Connection to "Capping of Roof Parapet"
                         If several installation parts require protection, it is advisable not to route the HVI power Conductor of each air-termination system individually
                         to the earth-termination system. The HVI power Conductors from the air-termination system can be connected to the capping of the roof
                         parapet which serves as a ring conductor. From the capping of the roof parapet several down conductors can then be led to the earth-ter-
                         mination system.








                                                                                                  l = sair x 2
                                                                                                 35 - max. 180 cm

                                                                                                            4


                                                                                          sair


                                                                                          l ≥ sair  1, 2  3
    HVI   power Conductor








                         Accessories for the Sealing End Range, Connection to "Capping of Roof Parapet"
         1
                         Spacer with EB element for HVI power Conductor (length of variable sealing end 350-900 mm)
                         Spacer for establishing the variable sealing end of the HVI power Conductor.
         Eurocode
                         With MV clamp for connection to the equipotential bonding (Rd 16 mm / Rd 8-10 mm).
                         Concrete base (Part No. 102 010, weight 17 kg) and base plate (Part No. 102 050) must be ordered separately.
                          Part No.                    105 462
                          PU                          1 pc(s)


         2               Variable tripod with EB element for HVI power Conductor (length of variable sealing end 900-1800 mm)

                         Tripod (hinged) with variable spacer for establishing the variable sealing end of the HVI power Conductor. For a variable sealing end length
                         of 900-1500 mm (Part No. 105 468) and 1500-1800 mm (Part No. 105 467).
         Eurocode
                         With UNI earthing clamp for connecting 1x Rd 8-10 mm and 1x conductor 4-50 mm². Adjustable to the roof inclination up to max. 10°. The
                         three concrete bases (Part No. 102 075, weight 8.5 kg) and base plates (Part No. 102 060) must be ordered separately.
                          Part No.                    105 468                     105 467
                          PU                          1 pc(s)                     1 pc(s)




         3               Spacer for HVI power Conductor
                         Spacer for additional mechanical fixing in the variable sealing end range.
                         The spacer is erected with two concrete bases (Part No. 102 010, weight 17 kg). The concrete bases and base plate (Part No. 102 050)
                         must be ordered separately.
                          Part No.                    106 814
                          PU                          1 pc(s)



                         KS connector
         4
                         With M10 screw and nut.
                         Lightning current carrying capabillity 200 kA (10/350 μs).
                          Part No.                    301 209
                          PU                          1 pc(s)