Page 42 - dehn-catalogue-safety-equipment_0
P. 42

PHE4 Voltage Detector  PHE III Voltage Detector  PHE Voltage Detector  PHG II Voltage Detector  Non-Contact Voltage Detector  PHE/G Voltage Detector  SPN Voltage Detector
        3. Verify that the Installation is dead – DEHNcheck Voltage Detectors


        HSA 194 High-Voltage Indicator
                                                             Nominal voltage range 110 ... 420 kV / 16.7 and 50 Hz
                                                             Easy and safe testing
                                                             •  For contactlessly verifying that switchgear and high-voltage
                                                               overhead lines or centre-earthed monophase traction power
                                                               lines are dead
                                                             •  Cost-effective / space-saving transport


                                                             General Information:
                                                             Temperature range        – 25 °C ... + 55 °C, climatic category N
                                                             For use in wet weather conditions  _
                                                             Indication               Acoustic and visual
                                                             Self-testing element     Yes
        High-voltage indicator used on a 110 kV overhead line.  Material (insulating stick)  Glass-fibre reinforced polyester tube
        Special instructions for the use of HSA 194 110 420 SN7737
        (Part No. 767539)
        The device can be switched between the “climbing check“ mode (switch
        position when climbing the tower) and the “110 ... 420 kV“ mode for
        verifying that the overhead conductor is dead.
    3. DEHNcheck Voltage Detectors  Switch position “climbing check”  General application notes for the HSA 194

        When climbing the lattice tower, the switch position “climbing check”
        allows to check from the corner leg whether the next overhead conductor
                                                             Switch position voltage range “110 … 420 kV“
        (or conductor bundle) is still energised when approaching it. During this
                                                             To verify absence of voltage from the tower cross arm, place the green
        check, the high-voltage indicator is moved closer towards the next over-
                                                             ring of the high-voltage indicator on the last earthed protective fitting (or
        head conductor and moved within 0.5 m (see Fig. 1). If the conductor is
        energised, there is a visual (red flashing light) and acoustic signal.
                                                             high-voltage indicator (see Fig. 2) points towards the overhead conductor
        The minimum distance A (min) (according to the nominal voltage in Table   earthed insulator cap) of the insulator so that the operating head of the
                                                             to be tested, which is attached to the other insulator end (longitudinal
        2) between the operating head of the high-voltage indicator and the over-  axis of the device in parallel to the longitudinal axis of the insulator). If
        head conductor must be observed.                     the conductor is energised, there is a visual (red flashing light) and acous-
        The customer must determine the maximum distance A (max) (safe trip-  tic signal.
        ping of the high-voltage indicator when approaching the overhead con-
        ductor) depending on the nominal voltage and document it in the oper-
        ating instructions.                                                                     Figure  2:  Example  of
        Using the high-voltage indicator when climbing lattice towers does not                  application  on  the
        replace verifying absence of voltage from the cross arm.                                tower  cross  arm  with
                                                                                                switch position “110 ...
                                                                                                420 kV“
                                                                      earthed    HSA 194
                                           Figure  1:  Example  of
          system I                  system II                         protective fitting
                                           application  on  the                   green ring
                                           corner  leg  of  a  lattice
                                           tower  with  switch  po-
                                           sition “climbing check“
             min. 0,5 m                    (only HSA 194 110 420
        min. 0,5 m  A (min.)               SN7737)
                                            Nominal   Min safety
                                            voltage  distance A                 insulator
          A (max.)
                                            110 kV  2000 mm
        minimum distance,                   220 kV  3000 mm
        see Table                           380 kV  4000 mm
           system I             system II   420 kV  4400 mm                   overhead conductor
           = disconnected       = energised
                                           Table
                                                                                           lG
                                                                               Ø43          lI



                         Nominal Voltage Range 110 ... 420 kV, with verification
                         while climbing the tower
        767 541   HSA194 110 420 STK
        767 542   HSA194 110 420 16.7
        767 541   4013364115712  05 00 03 06      1,2
        kg         1.597,00 €
        767 542   4013364086616  05 00 03 06      5,35
        kg         0,00 €  With plug-in coupling as end fitting for extending the handle.
        767 539   4013364306769  05 00 03 06      1.40
        kg         0,00 €  Storage bag included in delivery.
                          Type                        HSA194 110 420 STK  HSA194 110 420 16.7  HSA 194 110 420 SN7737
        767 539   HSA 194 110 420 SN7737
                          Part. No.                   767 541            767 542            767 539
                          Nominal voltage range  (UN)  110 ... 420 kV    110 ... 420 kV     110 ... 420 kV
                          Frequency                   50 Hz              16.7 Hz            50 Hz
                          Total length  (lG)          940 mm             940 mm             940 mm
                          Insulating clearance  (lI)  540 mm             540 mm             540 mm
                          Verification while climbing the tower  No      No                 Yes
                          DB drawing No.              —                  3 Ekgw 02.54       —