Page 39 - dehn-catalogue-safety-equipment_0
P. 39
PHE4 Voltage Detector PHE III Voltage Detector PHE Voltage Detector PHG II Voltage Detector Non-Contact Voltage Detector PHE/G Voltage Detector SPN Voltage Detector
3. Verify that the Installation is dead – DEHNcheck Voltage Detectors
PHG II Voltage Detector
Nominal voltages up to 20 kV / 50 Hz
Easy and safe testing
• Cost-effective
• Reliable indication
General Information:
Standard EN/IEC 61243-1 (DIN VDE 0682-411)
Temperature range –25 °C ... +55 °C, climatic category N
Design Complete
Only for indoor installations `
For Indoor installations
Indication Visual, 3 LEDs
Passive voltage detector without PHG II voltage detector used in a type-tested switchgear installation
Function
batteries
Material (test electrode) Cu/gal Sn
Material (test prod) Glass-fibre reinforced polyester tube
Material (indicator) Plastic
Material (insulating stick) Glass-fibre reinforced polyester tube
Test for correct operation 3. DEHNcheck Voltage Detectorsk
The EN 50110-1 (DIN VDE 0105-100) standard requires that voltage de- On the test prod of the voltage detector there is a fork-shaped electrode.
tectors be tested for correct operation directly before and after they are
used.
Voltage detectors without self-testing element must be tested for correct
operation by contacting parts of the installation connected to operating
voltage.
Nominal Voltages up to 20 kV / 50 Hz 766 706 766 710 766 720 PHG2 6 PHG2 10 PHG2 20
Category “S“ for indoor switchgear installations.
766 706 4013364094307 05 00 03 07 800 g
349,00 €
766 710 4013364094314 05 00 03 07 1.70
351,00 €
kg 766 720 4013364094321 05 00 03 07 1.70
lG kg 383,00 €
Ø24
lO
Ø20
Type PHG2 ... 6 10 20
Part. No. 766 706 766 710 766 720
Nominal voltage (UN) 6 kV 10 kV 20 kV
Total length (lG) 1425 mm 1425 mm 1425 mm
Insertion depth (IO) 720 mm 720 mm 720 mm
Valid as of January 1, 2019 You will find detailed product information on our website 37