Page 43 - dehn-catalogue-safety-equipment_0
P. 43

PHE4 Voltage Detector  PHE III Voltage Detector  PHE Voltage Detector  PHG II Voltage Detector  Non-Contact Voltage Detector  PHE/G Voltage Detector  SPN Voltage Detector
           3. Verify that the Installation is dead – DEHNcheck Voltage Detectors


           HSA 205 High-Voltage Indicator
           Nominal voltage range 1 ... 420 kV / 50 Hz
           •  For contactlessly verifying that switchgear installations and
            high-voltage overhead lines are dead
           •  Wide nominal voltage range



           General Information:
           Temperature range        –25 °C ... +55 °C, climatic category N
           For use in wet weather conditions  _
           Indication               Visual and acoustic
           Self-testing element     Yes
           Material (insulating stick)  Glass-fibre reinforced polyester tube
                                                                HSA 205 high-voltage indicator with insulating cap used on a switchgear instal-
                                                                lation.

           Application notes
           The operating head of HSA 205 high-voltage indicator is fitted with a
           yellow switching ring, which is used to set the required nominal
           voltage range, either 1 to 30 kV, 30 to 220 kV or 110 to 420 kV.
           The transparent insulating cap must be used in the voltage range from 1
           to 30 kV. Provided that the insulating tube and cap of the high-voltage
           indicator are in a dry and clean condition, the minimum distance A can be                                  3. DEHNcheck Voltage Detectorsk
           reduced for nominal voltages up to 30 kV.
           If these conditions cannot be ensured, the minimum distance A must be
           maintained!                                           e.g. switchgear installations 1 ... 30 kV  e.g. overhead lines  e.g. switchgear installations ≥ 110 kV


           Minimum distances A according to nominal voltage:
           Selected   Nominal voltage acc. to  Min. safety distance A                                    A
           voltage range  DIN VDE 0105 Part 1  DIN VDE 0105 Part 1
           Red        over     1 up to     6 kV      90 mm indoor installations
           1 ... 30 kV  over     6 up to   10 kV    120 mm indoor installations  A
                      over     1 up to   10 kV    150 mm outdoor installations
                      over   10 up to   20 kV    220 mm indoor and outdoor installations
                      over   20 up to   30 kV    320 mm indoor and outdoor installations     tower
           White      over   30 up to   45 kV    480 mm indoor and outdoor installations
           30 ... 220 kV  over   45 up to   60 kV    630 mm indoor and outdoor installations  A
                      over   60 up to 110 kV  1100 mm indoor and outdoor installations
                      over 110 up to 220 kV  2100 mm indoor and outdoor installations  9
           Yellow     over 110 up to 220 kV  2100 mm indoor and outdoor installations  conductor
           110 ... 420 kV  over 220 up to 420 kV  2900/3400 mm indoor and outdoor installations  9



           Nominal Voltage Ranges up to 420 kV,                  lG
           switchable                                             lI                                        767 552  767 547   HSA205 U 1 420 STK
                                                                                                             HSA205 U 1 420SN7608
           With  insulating  cap  and  plug-in  coupling  as  end   Ø43
           fitting for extending the handle.                                                                767 552  kg  767 547  kg        4013364115736  05 00 03 06        2,00  2,00
                                                                                                              1.911,00 €

                                                                                                             4013364158276  05 00 03 06

           Storage bag included in delivery.
           Type HSA205 U 1 ...         420 STK                      420SN7608
           Part. No.                   767 552                      767 547 +
           Nominal voltage range  (UN)  1 ... 30 / 30 ... 220 / 110 ... 420 kV  1 ... 30 / 30 ... 220 / 110 ... 420 kV
           Frequency                   50 Hz                        60 Hz
           Total length  (lG)          950 mm                       950 mm
           Insulating clearance  (lI)  540 mm                       540 mm


















           Valid as of January 1, 2019                       You will find detailed product information on our website   41