                                          THERMISTOR PROTECTION RELAY TER-7










       Features:
      »»
     » »  Universal supply AC/DC 24-240V
      »»
     » »  Monitors temperature in range of PTC thermistor
     » »  PTC sensor in motor windings
      »»
      »»
     » »  MEMORY function - manual reset
      »»
     » »  Possibility of remote reset
      »»
     » »  Monitoring short circuit or sensor disconnecting
      »»
     » »  Output contact: 2x changeover 8A
     » »  LED indication
      »»
     » »  1-MODULE, DIN rail mounting
      »»
        Technical parameters          TER-7               Description
        Function:             temperature of motor winding
        Supply Terminals:             A1 - A2
        Supply voltage:          AC 24-240V, DC 24V
        Consumption:                   2VA
        Supply voltage tolerance:   -15%; +10%
        Measuring   circuit
        Measuring terminals:          T1 - T2
        Cold sensor resistance:      50    - 1.5
        Upper level:                   3.3k
        Lower level:                   1.8k
        Sensor:                   PTC (part of motor)
        Sensor failure indication:    red LED
        Accuracy
        Accuracy in repetition:       <0.5%
        Switching difference:         +/-5%
        Temperature dependance:      <0.1%/ C
                                           0
        Output
        Number of contacts:      2 x changeover, (AgNi)
        Rated current:               8A / AC1             Connection, Functions
        Switching capacity:   2000 VA / AC1, 192 W / DC
        Inrush current:              10A / < 3s
        Switching voltage:       250V AC1 / 24V DC
        Min. breaking capacity DC:    500mW
        Output indication:            red LED
        Mechanical life:              3 x 10 7
        Electrical life (AC1):       0.7 x 10 5
        Other   information
        Operating temperature:      -20.. + 55 C
                                            0
        Storage temperature:        -30.. + 70 C
                                            0
        Electrical strength:     4 kV (supply - output)
        Operating position:            any                Function description
        Mounting:                 DIN rail EN 60715       The relay monitors temperature of the motor winding with a PTC thermistor which
        Protection:                    IP40               is mostly placed inside the motor winding. Resistance of the PTC
        Overvoltage category:           III               thermistor runs to a max 1.5 k    in the cold stage. When temperature increases the
        Pollution degree:               2                 resistance goes up and when it exceeds the limit of 3.3 k   ,the contact of output
        Max. cable size:    max. 2.5mm / with sleeve 1.5mm 2  relay switches off the contactor controlling the motor. When temperature decreases
                                     2
                                                          and thereby decreases thermistor resistance under 1.8 k   ,the output contact of the
        Dimensions:               90 x 17.6 x 64mm        relay again switches on.
        Weight:                        67g
        Standards:             EN 60730-2-9, EN 61010-1
                            IPD INDUSTRIAL PRODUCTS            Phone: 1300 556 601            www.ipdgroup.com.au