4. Mount the incoming and outgoing copper using
the set of busbar holders provided as shown.
(torque - 10 Nm)
Connect the outgoing copper bars to the outgo-
ing copper links with the M10 hexagon bolts pro-
vided. (torque - 49 Nm)
5. Mount the cable box with 04 screws
6. Insert the pre-wired control plug assembly in
through the side slot and screw in. Break the
flaps of the PC plates as required in order to take
the cables out.
7. Bend the PC retaining plate along the slotted
edge as shown. Make sure to bend it in the cor-
rect direction.
8. Break the flaps of the PC plates on the lid as
required for outgoing cables and fix the lid.
ISSUED BY: F. P DATE: 01.10.2007 APPROVED BY: A. K DATE: 01.10.2007 REPLACES: 01.04.2005 35