Page 114 - B_ELSB_Cat_2022_01_MCBs
P. 114
1/114 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
S800S - S200 P @ 230/400 V
E. S800S
Char. B
L. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
6 0.4 0.5 0.7 1 1.5 2.6
10 0.4 0.6 0.7 1 1.4
13 0.5 0.7 0.9 1.3
25
16 0.7 0.9 1.3
20 0.9 1.3
S200P B
25 0.9 1.3
32 0.8 1.1
40 0.8 1.1
15
50 1
63 0.9
E. S800S
Char. B
L. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
0.5 T T T T T T T T
1 3.3 T T T T T T T
1.6 0.6 1.3 T T T T T T
2 0.4 0.7 1.2 T T T T T
3 0.4 0.6 0.7 1.1 2.6 8.8 T
4 0.4 0.6 0.7 1 1.7 3.1 7
25 6 0.4 0.5 0.7 1 1.5 2.6
8 0.4 0.6 0.7 1 1.4
S200P C 10 0.4 0.6 0.7 1 1.4
13 0.5 0.7 0.9 1.3
16 0.7 0.9 1.3
20 0.9 1.3
25 0.9 1.3
32 0.8 1.1
40 0.8 1.1
15
50 1
63 0.9
E. = feed side
L. = load side
T = Total selectivity up to breaking capacity of the switch on load side
Selectivity limit values indicated in kA