Page 119 - B_ELSB_Cat_2022_01_MCBs
P. 119
1
1/119
—
MCBs technical details
Coordination tables: selectivity
S800S – S400E/S450E @230/400 V
Supply s. S800S
Char. B
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S400E B, C Icn [kA] 6 0.4 0.5 0.6 0.9 1.4 2.4
S450E 6 10 0.4 0.5 0.7 0.9 1.3
FS401E
FS451E 13 0.5 0.7 0.9 1.2
FS403E 16 0.7 0.9 1.2
FS453E
20 0.9 1.2
25 0.9 1.2
32 0.7 1
40 0.7 1
50 0.9
63 0.9
Supply s. S800S
Char. C
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S400E B, C Icn [kA] 6 0.4 0.5 0.6 0.9 1.3 2.2 4.4
S450E 6 10 0.3 0.4 0.5 0.6 0.8 1.2 1.8
FS401E
FS451E 13 0.3 0.4 0.5 0.6 0.8 1.2 1.7
FS403E 16 0.3 0.4 0.5 0.6 0.8 1.2 1.7
FS453E
20 0.4 0.5 0.6 0.8 1.1 1.6
25 0.4 0.5 0.6 0.8 1.1 1.6
32 0.4 0.5 0.7 0.9 1.3
40 0.5 0.7 0.9 1.3
50 0.7 0.9 1.2
63 0.8 1.1
Supply s. S800S
Char. D, K
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S400E B, C Icn [kA] 6 0.5 0.9 1.1 1.8 2.5 T T T
S450E 6 10 0.4 0.5 0.8 1 1.3 2.5 3.5 T
FS401E
FS451E 13 0.4 0.5 0.8 1 1.3 2.3 3 5.1
FS403E 16 0.5 0.8 1 1.3 2.3 3 5.1
FS453E
20 0.7 1 1.2 2.1 2.7 4.3
25 0.7 1 1.2 2.1 2.7 4.3
32 0.9 1 1.7 2.2 3.4
40 1 1.7 2.2 3.4
50 1.4 1.7 2.1
63 1.6 2.1