Page 117 - B_ELSB_Cat_2022_01_MCBs
P. 117
1
1/117
—
MCBs technical details
Coordination tables: selectivity
E. S800S
Char. D
L. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
6 0.5 1 1.2 2 2.8 9.9 21.3 T
10 0.4 0.6 0.8 1.1 1.4 2.8 3.9 7.4
13 0.4 0.6 0.8 1.1 1.4 2.5 3.3 5.6
25
16 0.6 0.8 1.1 1.4 2.5 3.3 5.6
20 0.8 1.1 1.3 2.3 3 4.7
S200P B
25 0.8 1.1 1.3 2.3 3 4.7
32 0.9 1.1 1.9 2.4 3.7
40 1.1 1.9 2.4 3.7
15
50 1.5 1.9 2.3
63 1.7 2.3
E. S800S
Char. D
L. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
0.5 T T T T T T T T
1 T T T T T T T T
1.6 T T T T T T T T
2 T T T T T T T T
3 0.7 2.2 4.4 T T T T T
4 0.7 1.3 2.2 4.4 7.7 T T T
25 6 0.5 1 1.2 2 2.8 9.9 22 T
8 0.4 0.6 0.8 1.1 1.4 2.8 3.9 7.4
S200P C 10 0.4 0.6 0.8 1.1 1.4 2.8 3.9 7.4
13 0.4 0.6 0.8 1.1 1.4 2.5 3.3 5.6
16 0.6 0.8 1.1 1.4 2.5 3.3 5.6
20 0.8 1.1 1.3 2.3 3 4.7
25 0.8 1.1 1.3 2.3 3 4.7
32 0.9 1.1 1.9 2.4 3.7
40 1.1 1.9 2.4 3.7
15
50 1.5 1.9 2.3
63 1.7 2.3
E. = feed side
L. = load side
T = Total selectivity up to breaking capacity of the switch on load side
Selectivity limit values indicated in kA