Page 118 - B_ELSB_Cat_2022_01_MCBs
P. 118
1/118 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
E. S800S
Char. D
L. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
0.2 T T T T T T T T
0.3 T T T T T T T T
0.5 T T T T T T T T
0.75 T T T T T T T T
1 T T T T T T T T
1.6 T T T T T T T T
2 2.3 T T T T T T T
3 0.7 1.3 4.4 T T T T T
25
4 0.7 1 2.2 4.4 7.7 T T T
6 0.6 0.8 1.5 2.5 3.6 12 24.2 T
S200P K
8 0.5 0.7 1.1 1.5 2 4 5.5 9.9
10 0.5 0.7 1.1 1.5 2 4 5.5 9.9
13 0.6 0.9 1.2 1.5 2.6 3.4 5.2
16 0.9 1.2 1.5 2.6 3.4 5.2
20 0.9 1.1 1.8 2.2 3.2
25 1.8 2.2 3.2
32 1.7 2 2.9
40 1.9 2.6
15
50 2.2
63
E. = feed side
L. = load side
T = Total selectivity up to breaking capacity of the switch on load side
Selectivity limit values indicated in kA