          MCBs technical details
          Coordination tables: selectivity




                           E.    S800S
                Char.            D
          L.          Icu [kA]   50
                           In [A]  25      32        40       50        63        80        100       125
                           0.2   T         T         T        T         T         T         T         T
                           0.3   T         T         T        T         T         T         T         T
                           0.5   T         T         T        T         T         T         T         T
                           0.75  T         T         T        T         T         T         T         T
                           1     T         T         T        T         T         T         T         T
                           1.6   T         T         T        T         T         T         T         T
                           2     2.3       T         T        T         T         T         T         T
                           3     0.7       1.3       4.4      T         T         T         T         T
                     25
                           4     0.7       1         2.2      4.4       7.7       T         T         T
                           6     0.6       0.8       1.5      2.5       3.6       12        24.2      T
          S200P K
                           8     0.5       0.7       1.1      1.5       2         4         5.5       9.9
                           10    0.5       0.7       1.1      1.5       2         4         5.5       9.9
                           13              0.6       0.9      1.2       1.5       2.6       3.4       5.2
                           16                        0.9       1.2      1.5       2.6       3.4       5.2
                           20                                  0.9      1.1       1.8       2.2       3.2
                           25                                                     1.8       2.2       3.2
                           32                                                     1.7       2         2.9
                           40                                                               1.9       2.6
                     15
                           50                                                                         2.2
                           63








































          E. = feed side
          L. = load side
          T  = Total selectivity up to breaking capacity of the switch on load side
              Selectivity limit values indicated in kA