          MCBs technical details
          Coordination tables: selectivity




                          E.    S800N
                Char.           B
          L.         Icu        36
                     [kA]  In [A]  25     32        40        50        63        80        100       125
                          0.5   T         T         T         T         T         T         T         T
                          1     0.8       5         T         T         T         T         T         T
                          1.6   0.5       1         2.3       T         T         T         T         T
                          2     0.3       0.5       0.7       2.3       T         T         T         T
                          3               0.4       0.5       0.7       1.2       2.5       8.6       T
                          4               0.4       0.4       0.7       1         1.7       3         7.7
                          6                                   0.6       0.8       1.2       2         3.6
                          8                                             0.7       0.9       1.3       2
          S200M D    15   10                                                      0.9       1.3       2
                          13                                                                1         1.5
                          16                                                                          1.5
                          20
                          25
                          32
                          40
                          50
                          63

                          E.    S800N
                Char.           B
          L.         Icu        36
                     [kA]  In [A]  25     32        40        50        63        80        100       125
                          0.5   T         T         T         T         T         T         T         T
                          1     0.8       5         T         T         T         T         T         T
                          1.6   0.5       1         2.3       T         T         T         T         T
                          2     0.3       0.5       0.7       2.3       T         T         T         T
                          3               0.4       0.5       0.7       1.2       2.5       8.6       T
                          4               0.4       0.4       0.7       1         1.7       3         7.7
                          6                                   0.6       0.8       1.2       2         3.6
                          8                                             0.7       0.9       1.3       2
          S200M  K   15   10                                                      0.9       1.3       2
                          13                                                                1         1.5
                          16                                                                          1.5
                          20
                          25
                          32
                          40
                          50
                          63










          E. = feed side
          L. = load side
          T  = Total selectivity up to breaking capacity of the switch on load side
              Selectivity limit values indicated in kA
   128   129   130   131   132   133   134   135   136   137   138