1/166 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
S750 - S300P @ 415V AC
Supply s. S750DR
Char. E, K
Load s. Icu [kA] 25
In [A] 16 20 25 35 40 50 63
6 T25 T25 T25 T25 T25 T25 T25
10 T25 T25 T25 T25 T25 T25 T25
13 T25 T25 T25 T25 T25 T25 T25
16 T25 T25 T25 T25 T25 T25
20 T25 T25 T25 T25 T25
S300P B 25
25 T25 T25 T25 T25
32 T25 T25 T25
40 T25 T25
50
63
S750 - S300P @ 415V AC
Supply s. S750DR
Char. E, K
Load s. Icu [kA] 25
In [A] 16 20 25 35 40 50 63
0,5...2 T25 T25 T25 T25 T25 T25 T25
3 T25 T25 T25 T25 T25 T25 T25
4 T25 T25 T25 T25 T25 T25 T25
6 T25 T25 T25 T25 T25 T25 T25
8 T25 T25 T25 T25 T25 T25 T25
10 T25 T25 T25 T25 T25 T25 T25
13 T25 T25 T25 T25 T25 T25 T25
S300P C 25
16 T25 T25 T25 T25 T25 T25
20 T25 T25 T25 T25 T25
25 T25 T25 T25 T25
32 T25 T25 T25
40 T25 T25
50
63