Page 170 - B_ELSB_Cat_2022_01_MCBs
P. 170
1/170 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
Fuse 100A+S750DR - S300P @ 415V AC
Supply s. Fuse 100A gG + S750DR
Char. E, K
Load s. Icu [kA] 25
In [A] 35 40 50 63 80 100
0,5...2 T25 T25 T25 T25
3 T25 T25 T25 T25
4 T25 T25 T25 T25
6 T25 20 20 20
8 20 20 15 15
10 20 15 15 15
13 15 15 15 15
S300P B, C 25
16 12 12 10 10
20 12 12 10 10
25 10 10 10
32 10 10
40 9
50
63
Fuse 100A+S750DR - S300P @ 415V AC
Supply s. Fuse 100A gG + S750DR
Char. E, K
Load s. Icu [kA] 25
In [A] 35 40 50 63 80 100
0,2...2 T25 T25 T25 T25
3 T25 T25 T25 T25
4 T25 T25 T25 T25
6 T25 20 20 20
8 20 20 15 15
10 20 15 15 15
13 15 15 15 15
S300P D, K 25
16 12 12 10 10
20 12 12 10 10
25 10 10 10
32 10 10
40 9
50
63
Fuse 100A+S750DR - S300P @ 415V AC
Supply s. Fuse 100A gG + S750DR
Char. E, K
Load s. Icu [kA] 25
In [A] 35 40 50 63 80 100
0,5...2 T25 T25 T25 T25
3 T25 T25 T25 T25
4 T25 T25 T25 T25
6 T25 T20 20 20
8 20 20 15 15
10 20 15 15 15
13 15 15 15 15
S300P Z 25
16 12 12 10 10
20 12 12 10 10
25 10 10 10
32 10 10
40 9
50
63