Page 169 - B_ELSB_Cat_2022_01_MCBs
P. 169
1
1/169
—
MCBs technical details
Coordination tables: selectivity
Fuse 80A+S750DR - S300P @ 415V AC
Supply s. Fuse 80A gG + S750DR
Char. E, K
Load s. Icu [kA] 25
In [A] 35 40 50 63 80 100
0,5...2 T25 T25 T25 T25
3 T25 T25 15 15
4 20 20 15 15
6 17 16 15 14
8 10 10 10 8
10 10 10 10 8
13 9 8 8 7
S300P B, C 25
16 9 8 8 7
20 8 7 7 6.5
25 7 6 6
32 6 5.5
40 5
50
63
Fuse 80A+S750DR - S300P @ 415V AC
Supply s. Fuse 80A gG + S750DR
Char. E, K
Load s. Icu [kA] 25
In [A] 35 40 50 63 80 100
0,2...2 T25 T25 T25 T25
3 T25 T25 15 15
4 20 20 15 15
6 17 16 15 14
8 10 10 10 8
10 10 10 10 8
13 9 8 8 7
S300P D, K 25
16 9 8 8 7
20 8 7 7 6.5
25 7 6 6
32 6 5.5
40 5
50
63
Fuse 80A+S750DR - S300P @ 415V AC
Supply s. Fuse 80A gG + S750DR
Char. E, K
Load s. Icu [kA] 25
In [A] 35 40 50 63 80 100
0,5...2 T25 T25 T25 T25
3 T25 T25 15 15
4 20 20 15 15
6 17 16 15 14
8 10 10 10 8
10 10 10 10 8
13 9 8 8 7
S300P Z 25
16 9 8 8 7
20 8 7 7 6.5
25 7 6 6
32 6 5.5
40 5
50
63