Page 168 - B_ELSB_Cat_2022_01_MCBs
P. 168
1/168 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
Fuse 63A+S750DR - S300P @ 415V AC
Supply s. Fuse 63A gG + S750DR
Char. E, K
Load s. Icu [kA] 25
In [A] 35 40 50 63 80 100
0,5...2 15 15 15 15
3 15 15 15 15
4 15 15 15 15
6 10 10 10 10
8 7 6 6 5
10 7 6 6 5
13 6 6 6 5
S300P B, C 25
16 6 6 6 6
20 5 6 6 6
25 6 6 6
32 4 3.5
40 3
50
63
Fuse 63A+S750DR - S300P @ 415V AC
Supply s. Fuse 63A gG + S750DR
Char. E, K
Load s. Icu [kA] 25
In [A] 35 40 50 63 80 100
0,2...2 15 15 15 15
3 15 15 15 15
4 15 15 15 15
6 10 10 10 10
8 7 6 6 5
10 7 6 6 5
13 6 6 6 5
S300P D, K 25
16 6 6 6 5
20 5 5 4.5 4.5
25 4.5 4.5 4
32 4 3.5
40 3
50
63
Fuse 63A+S750DR - S300P @ 415V AC
Supply s. Fuse 63A gG + S750DR
Char. E, K
Load s. Icu [kA] 25
In [A] 35 40 50 63 80 100
0,5...2 15 15 15 15
3 15 15 15 15
4 15 15 15 15
6 10 10 10 10
8 7 6 6 5
10 7 6 6 5
13 6 6 6 5
S300P Z 25
16 6 6 6 5
20 5 5 4.5 4.5
25 4.5 4.5 4
32 4 3.5
40 3
50
63