Page 192 - B_ELSB_Cat_2022_01_MCBs
P. 192

1/192            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          MCBs internal resistance, power loss and max. permissible earth-fault
          loop impedance


          Maximum permissible earth-fault loop impedance ZS at U0 =   Determined according to DIN VDE 0100-520 sheet
          230 V~ b to ensure compliance with the operation conditions   2:2002-11(source impedance = 300 mΩ and conductor
          pursuant to IEC 60364-4.                            temperature 70 °C. The internal resistance of the MCB is
          Operating time < 0.4 s; at 400 V~ < 0.2 s and at > 400 V~ <   already considered.
          0.1 s The instantaneous release of the MCB ensures an
          operating time of ≤ 0.1 s (TN system).



          S 200 and S 200 M
          Rated            B                C                D                K                Z
          current I  A
                n          max. ZS          max. ZS          max. ZS          max. ZS          max. ZS
                           q                q                q                q                q
          0.5               -                40.4             18.5             28.4             145.6
          1                 -                21.4             10.0             14.9              74.6
          1.6               -                13.5              6.3              9.4              46.8
          2                 -                10.8              5.1              7.5              37.6
          3                 -                 7.2              3.4              5.1              25.1
          3                 -                 7.2              3.4              5.1              25.1
          4                 -                 5.4              2.5              3.7              18.8
          6                 7.3               3.5              1.6              2.4              12.5
          8                 5.5               2.6              1.1              1.7               9.3
          10                4.3               2.0              0.8              1.3               7.4
          13                3.2               1.5              0.6              1.0                -
          16                2.6               1.1              0.4              0.7               4.5
          20                2.0               0.8              0.3              0.5               3.5
          25                1.5               0.6              0.2              0.4               2.8
          32                1.1               0.4              0.1              0.2               2.1
          40                0.9               0.3              0.0              0.1               1.6
          50                0.6               0.2              0.0              0.0               1.2
          63                0.4               0.1              0.0              0.0               0.9
          b U0 = rated voltage against earthed conductor; for U0 = 240 V~ is ZS · 1.04; for U0 = 127 V~ is ZS · 0.55