Page 2 - B_ELSB_Cat_2022_01_MCBs
P. 2

1/2              ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          Definitions according to standards for miniature circuit breakers




          Rated insulation voltage (Ui) according IEC/EN 60664-1:  IEC/EN 60947-2
          Root mean square (R.M.S.) withstand voltage value assigned   This part of the IEC/EN 60947 applies to circuit-breakers,
          by the manufacturer to the equipment or to a part of it,   the main contacts of which are intended to be connected to
          characterizing the specified (long-term) withstand capabil-  circuits, the rated voltage of which does not exceed 1.000
          ity of its insulation.                              V a.c. or 1.500 V d.c..
                                                              It applies whatever the rated currents, the method of
          NOTE:                                               construction or the proposed applications of the circuit-
          The rated insulation voltage is not necessarily equal to the rated voltage of
          the equipment which is primarily related to functional performance.  breakers may be.
                                                              The circuit-breakers are designed for use by instructed
          IEC/EN 60898-1                                      people.
          Miniature Circuit Breakers according IEC/EN 60898-1 are
          intended for the protection against overcurrents of wiring   Rated ultimate short-circuit breaking capacity Icu
          installations of buildings and similar applications; they are   The rated ultimate short-circuit breaking capacity of
          designed for use by uninstructed people and for not being   a circuit-breaker is the value of ultimate short-circuit
          maintained. This part of IEC/EN 60898 applies for a.c. air-  breaking capacity assigned to that circuit-breaker by the
          break circuit-breakers for operation at 50 Hz or 60 Hz,   manufacturer for the corresponding rated operational
          having a rated voltage not exceeding 440 V (between   voltage. It is expressed as the value of the prospective
          phases), a rated current not exceeding 125 A and a rated   breaking current, in kA (r.m.s. value of the a.c. component
          short-circuit capacity not exceeding 25.000 A.      in the case of a.c.).
          As far as possible, it is in line with the requirements
          contained in IEC/EN 60947-2.                        The sequence of operations shall be: O – t – CO.*

          Rated short-circuit capacity (Icn)                  Rated service short-circuit breaking capacity Ics
          The rated short-circuit capacity of a circuit-breaker is the   The rated service short-circuit breaking capacity of a circuit-
          value of the ultimate short-circuit breaking capacity   breaker is the value of service short-circuit breaking
          assigned to that circuit-breaker by the manufacturer.  capacity assigned to that circuit-breaker by the
          The sequence of operations shall be: O – t – CO.*   manufacturer for the corresponding rated operational
                                                              voltage. It is expressed as a value of prospective breaking
          Service short-circuit capacity (Ics)                current, in kA, corresponding to one of the specified
          A circuit-breaker having a given rated short-circuit   percentages of the rated ultimate short-circuit breaking
          capacity has a corresponding fixed service short-circuit   capacity and rounded up to the nearest whole number.
          capacity (Ics). This is therefore generally not indicated.  It may be expressed as a % of Icu (for example Ics = 25 % Icu).

          Rated operational voltage (Un)                      The sequence of operations shall be: O – t – CO – t – CO.*
          The rated voltage of a circuit-breaker is the value of voltage,
          assigned by the manufacturer, to which its performance   *  The following symbols are used for defining
          (particularly the short-circuit performance) is referred.  the sequence of operatons:
          The same circuit-breaker may be assigned a number of rated      O   represents an opening operation.
          voltages and associated rated short-circuit capacities.     CO represents a closing operation followed by an auto-
                                                                 matic opening.
          2The voltage which appears across the terminals of a pole of      t   represents the time interval between two short-cir-
          a circuit-breaker after the breaking of the current.   cuit operations.
          The value of the power frequency recovery voltage shall be
          equal to 110 % of the rated voltage of the circuit-breaker un-
          der test.