Page 5 - B_ELSB_Cat_2022_01_MCBs
P. 5

1
                                                                                                             1/5



          —
          MCBs technical details
          Tripping characteristics




          Tripping characteristics S 200 / S 200 M / S 200 P / S 200 S / S 200 MUC / SN 201 L / SN 201 / SN 201 M
                               AC                                                             DC
                               100 Hz               200 Hz               400 Hz
          Multiplier           1.1                  1.2                  1.5                  1.5
          The thermal tripping performance is independent from the network frequency

          Tripping characteristics SU200 M
                                                         1)
          Acc. to     Tripping    Rated current  Thermal release                Electromagnetic release  2)
                      characteristics
                                              Currents:              Tripping time  Range of instantaneous tripping Tripping
                                              conventional   conventional                               time
                                              non-tripping   tripping
                                              current    current
                                  In          I1         I2
          UL 489      C           0.5 to 63 A   1.03 · I n           > 1 h      5 · I n                 > 0.2 s
                                                         1.25 · I    < 1 h  3)              10 · I      < 0.2 s
                                                              n                                n
                      K           0.2 to 63 A   1.03 · I n           > 1 h      10 · I n                > 0.2 s
                                                         1.25 · I    < 1 h  3)              14 · I      < 0.2 s
                                                              n                                n
                      Z           0.5 to 63 A   1.03 · I             > 1 h      2 · I                   > 0.2 s
                                                  n                                n
                                                         1.25 · I n  < 1 h  3)              3 · I n     < 0.2 s
          1)   The thermal releases are calibrated to a nominal reference ambient temperature e.g. for UL 489 of 40°C.
          In the case of higher ambient temperatures, the current values fall by approx. 4 % for each 10 K temperature rise.
          2)  The indicated tripping values of electromagnetic tripping devices apply to a frequency of 50/60 Hz. The thermal release operates independent of frequency.
          3)  As from operating temperature (after I1 > 1h)


          Tripping characteristics S200 80-100A
          Acc. to      Tripping    Rated current  Thermal release               Electromagnetic release  2)
                                                          1)
                       characteristics
                                              Currents:             Tripping time  Range of instantaneous   Tripping time
                                                                                tripping
                                              conventional  conventional
                                              non-tripping  tripping
                                              current    current
                                   I  n       I1         I2
          IEC/EN 60898-1  B        80 up to 100 A  1.13 · I  n      > 2 h       3 · I n             0.1 ... 90 s
                                                         1.45 · I   < 2 h                  5 · I    < 0.1 s
                                                             n                                n
                       C           80 up to 100 A  1.13 · I  n      > 2 h       5 · I n             0.1 ... 30 s
                                                         1.45 · I   < 2 h                  10 · I   < 0.1 s
                                                             n                                n
          1)  The thermal releases are calibrated to a nominal reference ambient temperature; for B and C the reference value is 30 °C.
          In the case of higher ambient temperatures, the current values fall by approx. 6 % for each 10 K temperature rise.
          2)  The indicated tripping values of electromagnetic tripping devices apply to a frequency of 50/60 Hz. The thermal release operates independent of frequency.


          Tripping characteristics S 750 DR
          Tripping    Reference    Delayed overload tripping         Short-time delayed selective tripping
          characteristic  ambient   Conventional   Conventional  Tripping time  Delayed   Short-time  Tripping time
                      temperature
                                   non-        tripping              tripping    delayed
                                   tripping current  current         current     tripping current
                      T  1)
                       ref
                                   I  nt       I t        t          I tv        I tk         t
          E           30 °C        1.05 x l               ≥ 2 h      5 x l                    0.05 s < t <   5 s (l  ≤ 32 A)
           selective                    n                               n                                n
                                                                                              0.05 s < t < 10 s (l  > 32 A)
                                                                                                         n
                                               1.2 x l n  < 2 h                  6.25 x l n   0.01 s < t < 0.3 s
          K selective  30 °C       1.05 x l n             ≥ 2 h      8 x l n                  0.05 s < t < 10 s
                                               1.2 x l    < 2 h                  12 x l       0.01 s < t < 0.3 s
                                                   n                                 n
          1)  Reference ambient temperature 30 °C (in the case of higher ambient temperatures, the current values are reduced by ca. 5 % per each 10 K)
   1   2   3   4   5   6   7   8   9   10