1/4 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Tripping characteristics
Tripping characteristics S 200 / S 200 M / S 200 P / S 200 S / S 200 MUC / SN 201 L / SN 201 / SN 201 M / S200C
Thermal release Electromagnetic release
Acc. to Tripping characteristic Current: Tripping time Currents: Tripping
and rated current conventional conventional hold trip time
non-tripping tripping current at least at
current current surges
IEC/EN 60898-1 B 6 to 63 A 1.13 · I > 1 h 3 · I > 0.1 s
n n
1.45 · I n < 1 h 5 · I n < 0.1 s
C 0.5 to 63 A 1.13 · I > 1 h 5 · I > 0.1 s
n n
1.45 · I n < 1 h 10 · I n < 0.1 s
D 0.5 to 63 A 1.13 · I > 1 h 10 · I > 0.1 s
n n
1.45 · I < 1 h 20 · I < 0.1 s
n n
IEC/EN 60947-2 K 0.2 to 63 A 1.05 · I n > 1 h 10 · I n > 0.2 s
1.2 · I < 1 h 14 · I < 0.2 s
n n
1.5 · I n < 2 min.
6.0 · I > 2 s (T1)
n
Z 0.5 to 63 A 1.05 · I > 1 h 2 · I > 0.2 s
n n
1.2 · I n < 1 h 3 · I n < 0.2 s
The indicated electromagnetic tripping values apply to a frequency range of 16 2/3 ... 60 Hz. For different network
frequencies or direct current the values change according to the multiplier in the table below
The thermal releases are calibrated to a nominal reference ambient temperature; for Z and K, the value is 20 °C, for B and C = 30 °C.
In the case of higher ambient temperatures, the current values fall by ca. 6 % for each 10 K temperature rise.
As from operating temperature (after I 1 > 1 h or, as applicable, 2 h).
Tripping characteristics S300P
Acc. to Tripping Rated current Thermal release Electromagnetic release 1)
2)
characteristics
Currents: Tripping time Currents: Tripping
conventional conventional hold current trip at time
non-tripping tripping surges least at
current current
IEC/EN 60898-1 B 06 to 63 A 1.13 · I n > 1 h 3 · I n > 0.1 s
1.45 · I < 1 h 5 · I < 0.1 s
n n
C 0.5 to 63 A 1.13 · I n > 1 h 5 · I n > 0.1 s
1.45 · I < 1 h 10 · I < 0.1 s
n n
D 0.5 to 63 A 1.13 · I > 1 h 10 · I > 0.1 s
n n
1.45 · I n < 1 h 20 · I n < 0.1 s
IEC/EN 60947-2 K 0.2 to 63 A 1.05 · I n > 1 h 10 · I n > 0.2 s
1.3 · I < 1 h 3) 14 · I < 0.2 s
n n
Z 0.5 to 63 A 1.05 · I n > 1 h 2 · I n > 0.2 s
1.3 · I < 1 h 3) 3 · I < 0.2 s
n n
1) The indicated electromagnetic tripping values apply to a frequency range of 16 2/3... 60 Hz. For different network frequencies or direct current the values change
according to the multipler in the table below
2) The thermal releases are calibrated to a nominal reference ambient temperature; for Z and K, the value is 40°C, for B, C and D is 30°C. In the case of higher ambient
temperatures, the current values fall by ca. 6% for each 10 K temperature rise.
3) As from operating temperature (after I > 1h or, as applicable, 2h).