Page 6 - B_ELSB_Cat_2022_01_MCBs
P. 6

1/6              ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          Tripping characteristics




         Tripping characteristic S800
                                             Thermal release                  Electromagnetic release 
          Acc. to    Tripping characteristic and rated  Current    Tripping time   Current           Tripping time
                     current                 conventional   conventional       hold current   trip at least at
                                             non-tripping   tripping           surges
                                             current    current
          IEC/EN 60898- B       10 to 80 A   1.13 ∙ I   n          > 1 h      3 ∙ I   n             > 0.1 s
          1
                                                        1.45 ∙ I   n  < 1 h              5 ∙ I   n  < 0.1 s
                     C          10 to 80 A   1.13 ∙ I              > 1 h      5 ∙ I                 > 0.1 s
                                                 n                               n
                                                        1.45 ∙ I   n  < 1 h              10 ∙ I   n  < 0.1 s
                     D          10 to 80 A   1.13 ∙ I              > 1 h      10 ∙ I                > 0.1 s
                                                 n                                n
                                                        1.45 ∙ I    < 1 h                20 ∙ I     < 0.1 s
                                                             n                               n
          IEC/EN 60947- B       0.5 to 125 A   1.05 ∙ I   n        > 1 h      3.2 ∙ I   n           > 0.1 s
          2                                             1.3 ∙ I    < 1 h                 4.8 ∙ I    < 0.1 s
                                                            n                                n
                     C          0.5 to 125 A   1.05 ∙ I   n        > 1 h      6.4 ∙ I   n           > 0.1 s
                                                        1.3 ∙ I    < 1 h                 9.6 ∙ I    < 0.1 s
                                                            n                                n
                     D          0.5 to 125 A   1.05 ∙ I            > 1 h      10.4 ∙ I              > 0.1 s
                                                 n                                 n
                                                        1.3 ∙ I   n  < 1 h               15.6 ∙ I   n  < 0.1 s
                     K          0.5 to 125 A   1.05 ∙ I            > 1 h      10.4 ∙ I              > 0.1 s
                                                 n                                 n
                                                        1.2 ∙ I   n  < 1 h               15.6 ∙ I   n  < 0.1 s
                     KM         20 to 80 A                                     10.4 ∙ I              > 0.1 s
                                                                                   n
                                                                                          15.6 ∙ I   n  < 0.1 s
                     UCB (DC only)   0.5 to 125 A   1.05 ∙ I   n   > 1 h      4.8 ∙ I   n           > 0.1 s
                                                        1.3 ∙ I    < 1 h                 7.2 ∙ In   < 0.1 s
                                                            n
                     UCK (DC only)   0.5 to 125 A   1.05 ∙ I   n   > 1 h      8.8 ∙ I   n           > 0.1 s
                                                        1.2 ∙ I    < 1 h                 13.2 ∙ I    < 0.1 s
                                                            n                                 n
                     PV-SP      5 to 125 A   1.05 ∙ I   n          > 1 h      4.8 ∙ I   n           > 0.1 s
                     (DC only)                          1.3 ∙ I   n  < 1 h               6 ∙ I   n  < 0.1 s
          UL489      Z          10 to 100 A   1 ∙ I                > 1 h       3.2 ∙ I               > 0.1 s
                                               n                                  n
                                                        1.35 ∙ I   n  < 1 h               4.8 ∙ I   n  < 0.1 s
                     K          10 to 100 A   1 ∙ I                > 1 h       10.4 ∙ I              > 0.1 s
                                               n                                   n
                                                        1.35 ∙ I   n  < 1 h               15.6 ∙ I   n  < 0.1 s
                     UCZ (DC only)   10 to 80 A   1 ∙ I   n        > 1 h       8.8 ∙ I   n           > 0.1 s
                                                        1.35 ∙ I    < 1 h                 13.2 ∙ I    < 0.1 s
                                                             n                                n
          UL489B     PV-S (DC only)  5 A     1.13 ∙ I   n          > 1 h       4.8 ∙ I   n           > 0.1 s
                                                        1.3 ∙ I    < 1 h                  6 ∙ I      < 0.1 s
                                                            n                               n
          The indicated electromagnetic tripping values apply to a frequency of 50/60 Hz.
           The thermal release are calibrated to a nominal reference ambient temperature; for B, C, D, UCB and PVS it is 30 °C, for K, UCK it is 20 °C for Z, K and UCZ it is
           25 °C, for PVS acc. to UL489B it is 50 °C.
          t > 2 h for I  > 63 A
                  n
           t < 2 h for I  > 63 A
                  n
   1   2   3   4   5   6   7   8   9   10   11