          MCBs technical details
          Tripping characteristics




          Tripping characteristics S300P

          MCB Type S300P - B (3 ... 5 x In AC)                    MCB Type S300P - C (5 ... 10 x In AC)
          Tripping Characteristic IEC/EN 60898-1                  Tripping Characteristic IEC/EN 60898-1


                 I1 I2   I1= 1,13x In  I2= 1,45x In  ϑ R = 30°C           I1 I2  I1= 1,13x In  I2= 1,45x In  ϑ R = 30°C
          10000,000                                                10000,000
                          1  = tripping curve from cold state                     1  = tripping curve from cold state
                     1                                                        1
           1000,000           a= thermal tripping                  1000,000           a= thermal tripping
                              b= magnetic tripping                                    b= magnetic tripping
                   1                                                       1
            100,000                                                 100,000
          Tripping time [s]  10,000  a                             Tripping time [s]  10,000  a





             1,000                                                    1,000

                          AC                                                           AC
                             DC                                                           DC
             0,100                                                    0,100
                          b                                                          b
             0,010                                                    0,010
                 1       3  4 5  7 10           100                      1          5  7 10  15         100
                        Multiple of rated current [I / In]                       Multiple of rated current [I / In]





          MCB Type S300P - D (10 ... 20 x In AC)
          Tripping Characteristic IEC/EN 60898-1

                 I1 I2   I1= 1,13x In  I2= 1,45x In  ϑ R = 30°C
          10000,000
                          1  = tripping curve from cold state
                     1
           1000,000           a= thermal tripping
                              b= magnetic tripping
                   1
            100,000
          Tripping time [s]  10,000  a





             1,000



             0,100                AC
                                       DC
                                   b
             0,010
                 1               10 15  20  30  100
                        Multiple of rated current [I / In]
   4   5   6   7   8   9   10   11   12   13   14