1/90 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: back-up
Breaking capacities
Definition: B and C acc. to IEC EN 60 898, Icn
K and Z acc. to IEC EN 60 947-2, Icu
AC DC Back up protection up to
ultimate short-circuit
Type 1 phase 2/3 phases 1 phase capacity of short-circuit
Tripping characteristic protective device.
Nominal current 230 V 400 V Selective
133 V 230 V 60 V Fuse
133/230 V 230/400 V MCB
A kA/cosj kA/cosj kA/cosj kA/cosj kA/T ≤ ms gG S 750 DR
6 63 A 100 A
10 ... 20 6/0,7 6/0,7 100 A 100 A
S 200-B 25 ... 32 10/0,5 10/0,5 10/0,5 10/0,5 10/4,0 100 A 100 A
S 200 M-B (S 200 M-B) (S 200 M-B)
40 125 A 100 A
50 ... 63 160 A 100 A
0,5 ... 2 100 kA not required
3 ... 4 20 A –
6 40 A 100 A
S 200-C 8 6/0,7 6/0,7 63 A 100 A
S 200 M-C 10 ... 20 10/0,5 10/0,5 10/0,5 10/0,5 10/4,0 100 A 100 A
25 ... 32 (S 200 M-C) (S 200 M-C) 100 A 100 A
40 125 A 100 A
50 ... 63 160 A 100 A
0,5 ... 2 100 kA not required
3 20 A –
4 25 A –
S 200-K 6 ... 10 6/0,7 6/0,7 63 A 100 A
S 200 M-K 16 ... 20 10/0,5 10/0,5 10/0,5 10/0,5 10/4,0 80 A 100 A
25 ... 32 (S 200 M-K) (S 200 M-K) 100 A 100 A
40 125 A 100 A
50 ... 63 160 A 100 A
0,5 ... 2 100 kA not required
3 ... 4 20 A –
6 35 A 100 A
S 200-Z 8 6/0,7 6/0,7 40 A 100 A
S 200 M-Z 10 ... 16 10/0,5 10/0,5 10/0,5 10/0,5 10/4,0 63 A 100 A
20 ... 25 (S 200 M-Z) (S 200 M-Z) 80 A 100 A
32 ... 40 100 A 100 A
50 ... 63 125 A 100 A
1. In symmetrically eathed DC networks 2 pole MCBs can be applied at up to 125 V DC (series connection). In this case the breaking capactiy is one level higher compared to an
equivalent 1 pole installation. Polarity does not have to be considered. Thus any connection mode is permitted.
2. Back up protection is only required when the prospective short circuit current exceeds the rated breaking capacity.