1/90             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          Coordination tables: back-up




         Breaking capacities
         Definition:  B and C acc. to IEC EN 60 898, Icn
                   K and Z acc. to IEC EN 60 947-2, Icu
                                    AC                                           DC         Back up protection up to
                                                                                            ultimate short-circuit
          Type                      1 phase               2/3 phases             1 phase    capacity of short-circuit
          Tripping characteristic                                                           protective device.
          Nominal current                                 230 V       400 V                           Selective
                                    133 V      230 V                             60 V       Fuse
                                                          133/230 V   230/400 V                       MCB
                            A       kA/cosj    kA/cosj    kA/cosj     kA/cosj    kA/T ≤ ms  gG        S 750 DR
                            6                                                               63 A      100 A
                            10 ... 20          6/0,7                  6/0,7                 100 A     100 A
          S 200-B           25 ... 32  10/0,5  10/0,5     10/0,5      10/0,5     10/4,0     100 A     100 A
          S 200 M-B                            (S 200 M-B)            (S 200 M-B)
                            40                                                              125 A     100 A
                            50 ... 63                                                       160 A     100 A
                            0,5 ... 2  100 kA                                               not required
                            3 ... 4                                                         20 A      –
                            6                                                               40 A      100 A
          S 200-C           8                  6/0,7                  6/0,7                 63 A      100 A
          S 200 M-C         10 ... 20  10/0,5  10/0,5     10/0,5      10/0,5     10/4,0     100 A     100 A
                            25 ... 32          (S 200 M-C)            (S 200 M-C)           100 A     100 A
                            40                                                              125 A     100 A
                            50 ... 63                                                       160 A     100 A
                            0,5 ... 2  100 kA                                               not required
                            3                                                               20 A      –
                            4                                                               25 A      –
          S 200-K           6 ... 10           6/0,7                  6/0,7                 63 A      100 A
          S 200 M-K         16 ... 20  10/0,5  10/0,5     10/0,5      10/0,5     10/4,0     80 A      100 A
                            25 ... 32          (S 200 M-K)            (S 200 M-K)           100 A     100 A
                            40                                                              125 A     100 A
                            50 ... 63                                                       160 A     100 A
                            0,5 ... 2  100 kA                                               not required
                            3 ... 4                                                         20 A      –
                            6                                                               35 A      100 A
          S 200-Z           8                  6/0,7                  6/0,7                 40 A      100 A
          S 200 M-Z         10 ... 16  10/0,5  10/0,5     10/0,5      10/0,5     10/4,0     63 A      100 A
                            20 ... 25          (S 200 M-Z)            (S 200 M-Z)           80 A      100 A
                            32 ... 40                                                       100 A     100 A
                            50 ... 63                                                       125 A     100 A

         1. In symmetrically eathed DC networks 2 pole MCBs can be applied at up to 125 V DC (series connection). In this case the breaking capactiy is one level higher compared to an
         equivalent 1 pole installation. Polarity does not have to be considered. Thus any connection mode is permitted.
         2. Back up protection is only required when the prospective short circuit current exceeds the rated breaking capacity.