Page 87 - B_ELSB_Cat_2022_01_MCBs
P. 87
1
1/87
—
MCBs technical details
Coordination tables: back-up
S300P - S200M @ 415V AC
Supply s. S300P
B, C, D, K
25
Load s. Char. Icu [kA] ln [A]
10 16 25 32 40 50 63
0,2…16 25 25 25 25 25
20 25 25 25 25
25 25 25 25
B, C, D,
S200M 15 32 25 25
K, Z
40 25
50
63
S300P - SN201L @ 240V AC
Supply s. S300P
B, C, D, K
25
Load s. Char. Icu [kA] ln [A]
10 16 25 32 40 50 63
2…16 25 25 25 25 18
20 25 25 25 18
SN201L B, C 6 25 25 25 18
32 25 18
40 18
S300P - SN201 @ 240V AC
Supply s. S300P
B, C, D, K
25
Load s. Char. Icu [kA] ln [A]
10 16 25 32 40 50 63
2…16 25 25 25 25 25
20 25 25 25 25
B, D 10 25 25 25 25
32 25 25
40 25
SN201
2…16 25 25 25 25 25
20 25 25 25 25
C 10 25 25 25 25
32 25 25
40 25
S300P - SN201M @ 240V AC
Supply s. S300P
B, C, D, K
25
Load s. Char. Icu [kA] ln [A]
10 16 25 32 40 50 63
2…16 25 25 25 25 25
20 25 25 25 25
B, D 10 25 25 25 25
32 25 25
40 25
SN201M
2…16 25 25 25 25 25
20 25 25 25 25
C 10 25 25 25 25
32 25 25
40 20