Page 86 - B_ELSB_Cat_2022_01_MCBs
P. 86
1/86 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: back-up
S300P - SN201L 2 pole @ 240V AC
Supply s. S300P
B, C, D, K, Z
40
Load s. Char. Icu [kA] ln [A]
0,2…63
SN201L B, C 6 2…40 40
S300P - SN201 2 pole @ 240V AC
Supply s. S300P
B, C, D, K, Z
40
Load s. Char. Icu [kA] ln [A]
0,2…63
B, D 10 6…40 40
SN201
C 10 2…40 40
S300P - SN201M 2 pole @ 240V AC
Supply s. S300P
B, C, D, K, Z
40
Load s. Char. Icu [kA] ln [A]
0,2…63
B 10 6…40 40
SN201M
C 10 2…40 40
S300P - S200L @ 415V AC
Supply s. S300P
B, C, D, K
25
Load s. Carat. Icu [kA] ln [A]
10 16 25 32 40 50 63
0,5…16 25 25 25 25 25
20 25 25 25 25
25 25 25 25
S200L B, C, D 6 32 25 25
40 25
50
63
S300P - S200 @ 415V AC
Supply s. S300P
B, C, D, K
25
Load s. Char. Icu [kA] ln [A]
10 16 25 32 40 50 63
0,2…16 25 25 25 25 25
20 25 25 25 25
25 25 25 25
B, C, D,
S200 10 32 25 25
K, Z
40 25
50
63