Page 92 - B_ELSB_Cat_2022_01_MCBs
P. 92
1/92 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: back-up
Fuse gG - MCB S 200, S 200 M
Supply s. Fuse gG S 750 DR
240 V
Characteristic
Load s. In [A] In [A] In [A]
6 63 100
10...20 100 100
S200 B 25...32 100 100
S200 M
40 125 100
50...63 160 100
3...4 20 —
6 40 100
8 63 100
S200
S200 M C 10...20 100 100
25...32 100 100
40 125 100
50...63 160 100
3 20 —
4 25 —
6...10 63 100
S200 K 16...20 80 100
25...32 100 100
40 125 100
50...63 160 100
3...4 20 —
6 35 100
8 40 100
S200 Z 10...16 63 100
20...25 80 100
32...40 100 100
50...63 125 100
This table shows coordination between an MCB and the upstream fuse maximum current value. Combination of the two protections allows the breaking capacity to be
elevated up to that of the combined fuse.
I.e. downstream MCB breaker S 201-C16, upstream fuse with In up to 100 A (breaking capacity: 100 kA). MCB breaker protection up to 100 kA.