Page 96 - B_ELSB_Cat_2022_01_MCBs
P. 96
1/96 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
Fuse - SN201 @ 230/240 V
Im Icu [kA]
In [A] 25 32 40 50 63 80 100 125
6 2 1.5 2.5 T T T T T T
6 4 1 2 4.5 T T T T T
6 6 1 1.5 4 4.5 T T T T
6 10 1.2 3.5 4 T T T T
SN201 L B-C 6 16 1 3 3.5 5 T T T
6 20 1 3 3.5 5 T T T
6 25 1 2 3 4.5 T T T
6 32 1 2 3 4.5 5 T T
6 40 1.5 2.5 4 5 T T
10 2 1.5 2.5 5 T T T T T
10 4 1 2 4.5 5 T T T T
10 6 1 1.5 4 4.5 7 T T T
10 10 1.2 3.5 4 6 T T T
SN201 B-C-D 10 16 1 3 3.5 5 T T T
10 20 1 3 3.5 5 8 T T
10 25 1 2 3 4.5 6.5 T T
10 32 1 2 3 4.5 5 8 T
10 40 1.5 2.5 4 5 6.5 T
10 2 1.5 2.5 5 7 T T T T
10 4 1 2 4.5 5 8 T T T
10 6 1 1.5 4 4.5 7 T T T
10 10 1.2 3.5 4 6 T T T
SN201
M B-C 10 16 1 3 3.5 5 9 T T
10 20 1 3 3.5 5 8 T T
10 25 1 2 3 4.5 6.5 9 T
10 32 1 2 3 4.5 5 8 T
10 40 1.5 2.5 4 5 6.5 9