Page 230 - IPD Product Catalog V17
P. 230
Lightning & Surge Protection
Selection Chart
Surge I Lightning I Recommended Maximum
Config Zone Boundary SPD Location Type/class max imp Model style/mounting Voltage Protection Level Up Model Style/Mounting Voltage Protection Level Up
8/20μs 10/350μs Backup Protection
500 A aG
Main switchboard Type 1 50 kA SG3-50-275 ≤ 1.3 kV XLP3-6M12
Distribution board Class I Spark gap-DIN 1.2/50µs 3 x NHG2-500
LPZ 0A/1 Service entrance Lightning
High lightning area (Ng>5) protection DVCI 1 255-TNC Integrated fuse
Location category C3 25 kA Spark gap-DIN mtg ≤ 1.5 kV external backup not
required
DVACSP1P255FM (x3) 125 A gG
250 kA 25 kA EBDG100013 ≤ 1.5 kV 3 x CMS221
Spark gap-DIN mtg 3 x 22G125
100 A gG
SD3-200-275
200 kA 25 kA ≤ 1.7 kV 3 x CMS221
MultiMOV-panel
Main switchboard Type 1 + 2 3 x 22G100
Service entrance Class I + II 150 kA 19 kA SD3-150-275 ≤ 1.6 kV 80 A gG
3 x CMS221
Sub switchboard
Combined
MEN Link installed LPZ 0A/1 High lightning area (Ng>2) protection 125 kA 12.5 kA DSH TNC 255 FM ≤ 1.5 kV 125 A gG
MultiMOV-panel
3 x 22G80
Distribution board
lightning
Industrial and commercial
and surge
3 x CMS221
Spark gap-DIN mtg
Long service lines
current
3 x 22G125
Location category C2 or C3
arrester
SD3-100-275
12.5 kA
100 kA
3 x CMS221
MultiMOV-panel ≤ 1.5 kV 63 A gG
3 x 22G63
63 A gG
IDD3-100-D480
100 kA 12.5 kA ≤ 1.5 kV 3 x CMS221
MOV-DIN
3 x 22G63
32 A gG
DGM TNC 385 CN FM IDD3-50-D480
Domestic service entrance 50 kA MOV-DIN mtg ≤ 1.5 kV MOV-DIN ≤ 1.5 kV 3 x CMS221
Services shielded 3 x 22G32
from direct strike Type 2 Integrated fuse
LPZ 0B/1 Major submains Class II 40 kA DGM TNC ACI 275 FM ≤ 1.5 kV external backup not
LPZ 1/2 Surge current MOV-DIN mtg
Short final subcircuits required
Load centres arrester 125 A gG
Location category B or C1 40 kA DGM TNC 275 FM ≤ 1.5 kV 3 x CMS221
MOV-DIN mtg
3 x 22G125
500 A aG
Main switchboard Type 1 50 kA SG3-50-275-N ≤ 1.3 kV XLP3-6M12
Distribution board Class I Spark gap-DIN mtg 1.2/50µs 3 x NHG2-500
LPZ 0A/1 Service entrance Lightning
High lightning area (Ng>5) protection DVCI 1 255-TT Integrated fuse
Location category C3 25 kA Spark gap-DIN mtg ≤ 1.5 kV external backup not
required
DVACSP1P255FM(x3) 125 A gG
250 kA 25 kA DGPM1255FM(x1) ≤ 1.5 kV 3 x CMS221
EB1413 3 x 22G125
100 A gG
SDN3-200-275
200 kA 25 kA ≤ 1.7 kV 3 x CMS221
MultiMOV-DIN
Main switchboard Type 1 + 2 3 x 22G100
Service entrance Class I + II 150 kA 19 kA SDN3-150-275 ≤ 1.6 kV 80 A gG
NO MEN Link installed LPZ 0A/1 High lightning area (Ng>2) protection 125 kA 12.5 kA DSH TT 255 FM ≤ 1.5 kV ≤ 1.6 kV 125 A gG
3 x CMS221
Combined
Sub switchboard
MultiMOV-DIN
3 x 22G80
Distribution board
lightning
Industrial and commercial
and surge
3 x CMS221
Spark gap-DIN mtg
current
Long service lines
3 x 22G125
Location category C2 or C3
arrester
63 A gG
SDN3-100-275
≤ 1.5 kV
3 x CMS221
12.5 kA
100 kA
MultiMOV-DIN
3 x 22G63
63 A gG
SDD3-100-275-A
100 kA 12.5 kA ≤ 1.5 kV 3 x CMS221
MOV-DIN
3 x 22G63
Domestic service entrance DGM TT 385 CN FM SDD3-50-275-A 32 A gG
Distribution boards 50 kA MOV-DIN mtg ≤ 1.5 kV MOV-DIN ≤ 1.5 kV 3 x CMS221
Consumer units Type 2 3 x 22G32
Load centres Integrated fuse
LPZ 0B/1 Class II DGM TT ACI 275 FM
LPZ 1/2 Services shielded from Surge current 40 kA MOV-DIN mtg ≤ 1.5 kV external backup not
direct strike arrester required
Major submains 125 A gG
Short final subcircuits 40 kA DGM TT 275 FM ≤ 1.5 kV 3 x CMS221
Location category B or C1 MOV-DIN mtg 3 x 22G125
230 1300 556 601 | ipd.com.au | V17-R05