                                SPARK GAP COMBINED LIGHTNING CURRENT AND SURGE ARRESTERS
                                 Imax                              Prospective  Voltage
                                 (8/20μs)   In (8/20μs)   Iimp   Connection  Fault   Protection  Integral   Signal
                                 (kA)    (kA)     (10/350μs)   Type  Rating   Level - Up  Fuse  C/O   Part No.
                                 According        (kA)             (kArms)  (kV)           Contact
                                 to AS1768
                                 MSB
                                 250     25       25      1+0      100      ≤ 1.5   Yes    Yes    DVCI1255FM
                                 250     25       25      1+0      25       ≤ 1.5   No     Yes    DVACSP1P255FM
                                 250     25       25      3+0 KIT  100      ≤ 1.5   Yes    Yes    DVCI1255-TNC
                                 125     12.5     12.5    3+0      25       ≤ 1.5   No     Yes    DSHTNC255FM
                DVCI1255FM




                                TYPE 1+2 - WITHOUT MEN LINK
                                SPARK GAP COMBINED LIGHTNING CURRENT AND SURGE ARRESTERS
                                 Imax                              Prospective  Voltage
                                 (8/20μs)   In (8/20μs)   Iimp   Connection  Fault   Protection  Integral   Signal
                                 (kA)    (kA)     (10/350μs)   Type  Rating   Level - Up  Fuse  C/O   Part No.
                                 According        (kA)             (kArms)  (kV)           Contact
                                 to AS1768
                                 MSB
                                 125     12.5     12.5    1+1      25       ≤ 1.5   No     Yes    DSHTT2P255FM
                                 250     25       25      3+1 KIT  100      ≤ 1.5   Yes    Yes    DVCI1255-TT
               DSHTNC255FM       125     12.5     12.5    3+1      25       ≤ 1.5   No     Yes    DSHTT255FM




                                TYPE 1+2+3 - WITH MEN LINK
                                SPARK GAP COMBINED LIGHTNING CURRENT AND SURGE ARRESTER
                                 Imax
                                 (8/20μs)         Iimp             Prospective  Voltage    Signal
                                 (kA)    In (8/20μs)   (10/350μs)   Connection  Fault   Protection  Integral   C/O   Part No.
                                 According   (kA)  (kA)   Type     Rating   Level - Up  Fuse  Contact
                                 to AS1768                         (kArms)  (kV)
                                 MSB
               DVM2TNC255FM      250     25       25      3+0      100      ≤ 1.5   No     Yes    DVM2TNC255FM




                                TYPE 1+2+3 - WITHOUT MEN LINK
                                SPARK GAP COMBINED LIGHTNING CURRENT AND SURGE ARRESTERS
                                 Imax                              Prospective  Voltage
                                 (8/20μs)   In (8/20μs)   Iimp   Connection  Fault   Protection  Integral   Signal
                                 (kA)    (kA)     (10/350μs)   Type  Rating   Level - Up  Fuse  C/O   Part No.
                                 According        (kA)             (kArms)  (kV)           Contact
                                 to AS1768
                                 MSB
                                 250     25       25      1+1      100      ≤ 1.5   No     Yes    DVM2TT2P255FM
               DVM2TT255FM
                                 250     25       25      3+1      100      ≤ 1.5   No     Yes    DVM2TT255FM