Page 232 - IPD Product Catalog V17
P. 232
Lightning & Surge Protection
POWER PROTECTION - SURGE DIVERTERS
TYPE 1+2 - WITH MEN LINK
SPARK GAP COMBINED LIGHTNING CURRENT AND SURGE ARRESTERS
Imax Prospective Voltage
(8/20μs) In (8/20μs) Iimp Connection Fault Protection Integral Signal
(kA) (kA) (10/350μs) Type Rating Level - Up Fuse C/O Part No.
According (kA) (kArms) (kV) Contact
to AS1768
MSB
250 25 25 1+0 100 ≤ 1.5 Yes Yes DVCI1255FM
250 25 25 1+0 25 ≤ 1.5 No Yes DVACSP1P255FM
250 25 25 3+0 KIT 100 ≤ 1.5 Yes Yes DVCI1255-TNC
125 12.5 12.5 3+0 25 ≤ 1.5 No Yes DSHTNC255FM
DVCI1255FM
TYPE 1+2 - WITHOUT MEN LINK
SPARK GAP COMBINED LIGHTNING CURRENT AND SURGE ARRESTERS
Imax Prospective Voltage
(8/20μs) In (8/20μs) Iimp Connection Fault Protection Integral Signal
(kA) (kA) (10/350μs) Type Rating Level - Up Fuse C/O Part No.
According (kA) (kArms) (kV) Contact
to AS1768
MSB
125 12.5 12.5 1+1 25 ≤ 1.5 No Yes DSHTT2P255FM
250 25 25 3+1 KIT 100 ≤ 1.5 Yes Yes DVCI1255-TT
DSHTNC255FM 125 12.5 12.5 3+1 25 ≤ 1.5 No Yes DSHTT255FM
TYPE 1+2+3 - WITH MEN LINK
SPARK GAP COMBINED LIGHTNING CURRENT AND SURGE ARRESTER
Imax
(8/20μs) Iimp Prospective Voltage Signal
(kA) In (8/20μs) (10/350μs) Connection Fault Protection Integral C/O Part No.
According (kA) (kA) Type Rating Level - Up Fuse Contact
to AS1768 (kArms) (kV)
MSB
DVM2TNC255FM 250 25 25 3+0 100 ≤ 1.5 No Yes DVM2TNC255FM
TYPE 1+2+3 - WITHOUT MEN LINK
SPARK GAP COMBINED LIGHTNING CURRENT AND SURGE ARRESTERS
Imax Prospective Voltage
(8/20μs) In (8/20μs) Iimp Connection Fault Protection Integral Signal
(kA) (kA) (10/350μs) Type Rating Level - Up Fuse C/O Part No.
According (kA) (kArms) (kV) Contact
to AS1768
MSB
250 25 25 1+1 100 ≤ 1.5 No Yes DVM2TT2P255FM
DVM2TT255FM
250 25 25 3+1 100 ≤ 1.5 No Yes DVM2TT255FM
232 1300 556 601 | ipd.com.au | V17-R05