Page 238 - Product Catalog V17 - Flip Book PDF
P. 238
Power Supplies & Transformers
AC UPS AMPLON FAMILY - RT SERIES
RT-PRO SERIES ON-LINE SINGLE PHASE UPS
Features: Output Voltage Power Rating
- Improves to unity output power factor AC (V) (kVA) (kW) Output Connections Model Part No.
- Improved efficiencies IEC C13 ×2, UPS102R2RT1B0BB
- Integrated dry-contacts with user- 1 1 Programmable RT Pro-1K
selectable definition (1) (1) IEC C13 ×2 ×2 groups UPS102R2RT1B0BB-M(*)
- Remote shutdown via it’s repo port 200 / 208 / IEC C13 x2, IEC C19 x1, UPS202R2RT1B0BB
220/ 230/240
- Convertible rack and tower configuration VAC , 1P2W+PE 2 2 Programmable RT Pro-2K
(1)
with rotatable LCD screen IEC C13 x2 x2 groups UPS202R2RT1B0BB-M(*)
- Load management IEC C13 x2, IEC C19 x1, UPS302R2RT1B0BB
- Support for external batteries to expand 3 3 Programmable RT Pro-3K
your runtime IEC C13 x2 x2 groups UPS302R2RT1B0BB-M(*)
(1) Derating to 90% load
(*) Shorter lead time item
UPS102R2RT1B0BB
RT-PRO SERIES ON-LINE SINGLE PHASE UPS SELECTION CHART
Model RT Pro-1K RT Pro-2K RT Pro-3K
Topology Online double-conversion
1kVA 2kVA 3kVA
Power Rating
1kW 2kW 3kW
Input
Nominal Voltage 200 / 208 / 220 / 230 / 240 VAC, 1P2W+PE
Voltage Range 175 - 280 VAC (100% load); 120 - 175 VAC (with derating to 70-100% load)
Frequency Range 40 - 70 Hz
Power Factor 0.99 (100% load)
Connection IEC C14 IEC C20
Output
Nominal Voltage 200 / 208 / 220 / 230 / 240 VAC, 1P2W+PE
(2)
(2)
Voltage Regulation ±3% (linear load)
Frequency 50/60 ± 0.05 Hz
Total Harmonic Distortion (THDv) ≤ 2% (linear load)
Power Factor 1
Connection IEC C13 ×2, Programmable IEC C13 ×2 ×2 groups IEC C13 x2, IEC C19 x1, Programmable IEC C13 x2 x2 groups
Overload Capability < 105% continuous; 105-125%: 1 min ± 5 secs; 126-150%: 15 ± 3 secs; 151-155%: 0.1 secs
Current Crest Ratio 3:1
Efficiency
Online Mode 93.50% 94% 94.30%
ECO Mode 99%
Battery
Battery Type VRLA
Nominal Voltage 24VDC 48VDC 72VDC
Quantity 2 pcs 4 pcs 6 pcs
Runtime 100% Load: 2.4 mins 2.5 mins 2.7 mins
70% Load: 4.6 mins 4.9 mins 5.2 mins
Charge Current Up to 2.5 A
Communication Interface
Display LCD display with LED indicators
Port USB, RS-232, REPO, Mini Slot, Input dry contact x1, Output dry contact x3
REPO (Emergency Power Off) Standard
Physical
Dimensions (W x H x D) 440 x 88 x 335 mm 440 x 88 x 430 mm 440 x 88 x 565 mm
Net Weight 11.7kg 21kg 28kg
Packing Dimensions (W x H x D) 484 x 220 x 579 mm 594 x 220 x 508 mm 605 x 220 x 1005 mm
Packing Weight 18kg 28.8kg 38kg
Environment
Operating Temperature 0 to 55°C (3)
Humidity 5-95% (non-condensing)
Audible Noise < 40 dBA Eco/ 48 dbA AC Mode
Altitude 0-3000 m (derating 1%/100 m from 1,000-3,000 m)
Ingress Protection Level IP20
Conformance
Safety CE, UL, cUL, RCM, UKCA
EMC IEC 62040-2
Sustainability RoHS, REACH
(2) Derating to 90% load
(3) 40 to 50°C de-rating to 90% load; 50 to 55°C de-rating to 75% load
All specifications are subject to change without prior notice.
238 1300 556 601 | ipd.com.au | V17-R12